§ 49-61 — Backflow prevention assemblies; approved list
Scottsdale Revised Code (Supp. No. 80: codified through Ordinance No. 4681, adopted July 1, 2025) · Scottsdale Revised Code § 49-61
Corpus is an independent public-information project, not the official City of Scottsdale website. Stable reference: corpuslaw.us/code/d5b4846d-b339-4afb-b528-5e711fa642d1
Sec. 49-61. - Backflow prevention assemblies; approved list.
(a) All backflow devices, independent of design and application, must be "lead free" as defined in 40 Code of Federal Regulations (CFR) 143, Subpart B and the Safe Drinking Water Act Section 1417. The following are the recognized types of backflow prevention assemblies which the Water Resources Division may require under section 49-59 or section 49-62. (1) Air gap: The unobstructed vertical distance through free atmosphere between the lowest point of a water supply outlet, pipe or faucet supplying potable water to a tank, plumbing fixture or other device and the flood level rim of the tank, plumbing fixture or other device. An approved air gap shall be at least twice the diameter of the supply pipe or faucet and in no case less than one (1) inch. (2) Reduced pressure principle assembly (hereinafter "RP"): A backflow prevention assembly containing two independently acting approved check valves together with a hydraulically operating, mechanically independent pressure differential relief valve located between the check valves, and at the same time below the first check valve. The assembly shall include properly located test cocks and tightly closing shut-off valves at each end of the assembly. (3) Double check valve assembly (hereinafter "DC"): A backflow prevention assembly composed of two independently acting, approved check valves, including tightly closing shut-off valves located at each end of the assembly and fitted with properly located test cocks. (4) Pressure vacuum breaker assembly (hereinafter "PVB"): A backflow prevention assembly containing an independently operating, loaded check valve and an independently operating, loaded air inlet valve located on the discharge side of the check valve. The assembly shall be equipped with properly located test cocks and tightly closing shut-off valves located at each end of the assembly. (b) A user may use a backflow prevention assembly if it has received the approval of the Foundation for Cross-Connection Control and Hydraulic Research of the University of Southern California, the American Society of Sanitary Engineering or other recognized testing agency approved by the Water Resources Division, and its use is approved by the division. Approved assemblies must have a local manufacturer's parts and service center.
Ask a question about Scottsdale law
Corpus searches the Scottsdale sections it holds and shows the ones that match, with their citations. Free, no sign-in.