257-18. Light and Ventilation; Habitable Rooms.
1. Kitchens, dining rooms and other rooms, excepting living and sleeping rooms, need not be provided with windows if such rooms have openings in the common walls with rooms having windows. The areas of these openings shall be at least 25% of the area of the room without openings, but in no case less than 20 square feet. 2. An exhaust fan with a capacity of at least 50 CFM shall be provided in any such room without windows when any portion of the required openings is equipped with doors. Such exhaust shall discharge to the outside, directly or by means of a duct. Doors used in required openings shall have louvered openings of at least 50% of the door area. 3. An exhaust fan with a capacity of 50 CFM shall be provided in any kitchen without windows when the area in the common wall between the kitchen and the room with windows is less than 50% of the floor area of the kitchen. The fan shall discharge to the outside, directly or by means of a duct. 4. Rooms without windows shall have their floor area added to the room with windows when determining the required window area for such room without windows.