Sec. 49-1421. - Accessibility to cleanouts.

Accessibility to cleanouts shall be as follows: (a) Vertical piping up to two inches in diameter: a minimum of 12 inches of horizontal service space in front of the cleanout. (b) Vertical piping exceeding two inches in diameter: a minimum of 18 inches of horizontal service space in front of the cleanout. (c) All sizes of vertical piping: a minimum 30 inches of vertical service space. (d) Cleanouts shall be directly accessible from a finished, service or storage space without the use of extraordinary equipment. However, cleanouts in dwelling units may be located within 20 feet of an access door or trap door. (e) Unless installed under an approved cover plate, cleanouts shall be installed above grade, readily accessible, and located to serve the purpose for which they are intended. Clearance requirements for service shall also apply to cleanouts installed under an approved cover plate.

(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 43, 8-13-21)