North Las Vegas Municipal Code § 13.20.060
in effect13.20.060 - Policy.
A. No water service connection to any premise shall be installed or maintained by the city unless the water supply is protected as required by city laws and regulations and this chapter. Service of water to any premise shall be discontinued by the city if a backflow prevention assembly required by this chapter is not installed, tested and maintained, or it is found that a backflow prevention assembly has been removed, bypassed, or if an unprotected cross-connection exists on the premises. Service will not be restored under such conditions or defects are corrected.
B. The consumer's system should be open for inspection at all reasonable times to authorized representatives of the city or the health agency having jurisdiction to determine whether unprotected cross-connections or other structural or sanitary hazards, including violations of these regulations, exist. When such a condition becomes known, the manager of utilities operations shall deny or immediately discontinue service to the premises by providing for a physical break in the service line until the consumer has corrected the condition(s) in conformance with the city's statutes relating to plumbing and water supplies and the regulations adopted hereto.
C. An approved backflow prevention assembly shall also be installed on each service line to a consumer's water system at or near the property line, but in all cases, before the first branch line leading off the service line wherever the following conditions exist:
1. In the case of premises having auxiliary water supply which is or may not be of safe bacteriological or chemical quality and which is not acceptable as an additional source by the manager of utilities operations or the health agency having jurisdiction, the public water system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line commensurate with the degree of hazard.
2. In the case of premises on which any industrial fluids or any other objectionable substance is handled in such a fashion as to create an actual or potential hazard to the public water system, the public system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line commensurate with the degree of hazard. This shall include the handling of process waters and waters originating from the city's system which have been subject to deterioration in quality.
3. In the case of premises having (1) internal cross-connections that cannot be permanently corrected or protected against, or (2) intricate plumbing and piping arrangements or where entry to all portions of the premises are not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not dangerous cross-connections exist, the public water system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line.
D. The type of protective assembly required under subsections (C)(1), (C)(2) and (C)(3)of this section shall depend upon the degree of hazard which exists as follows:
1. In the case of any premise where there is an auxiliary water supply as stated in subsection (C)(1) of this section and it is not subject to any of the following rules, the public water system shall be protected by any approved air gap or an approved reduced pressure principle backflow prevention assembly.
2. In the case of any premise where there is water or a substance that would be objectionable but not hazardous to health, if introduced into the public system, the public water system shall be protected by an approved double check valve backflow prevention assembly.
3. In the case of any premise where there is any material dangerous to health which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved air gap or and approved reduced pressure principle backflow prevention assembly. Examples of premises where these conditions will exist include sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries and plating plants.
4. In the case of any premise where there are unprotected cross-connections, either actual or potential, the public water system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly at the service connection.
5. In the case of any premise where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete in-plant cross-connection survey, the public water system shall be protected against backflow from the premises by either an approved air gap or an approved reduced pressure principle backflow preventer on each service to the premise.
E. 1.
Any backflow prevention assembly required herein shall be a make, model and size approved by the manager of utilities operations. The term "approved backflow prevention assembly" means an assembly that has been manufactured in full conformance with the standards established by the American Water Works Association entitled:
AWWA/ANSI C510-92* Standard for Double Check Valve Backflow Prevention Assemblies;
AWWA/ANSI C511-92* Standard for Reduced Pressure Principle Backflow Prevention Assemblies;
and, have met completely the laboratory and field performance specifications of the Foundation for Cross-Connection Control and Hydraulic Research of the University of Southern California (USC FCCCHR) established in:
Specifications of Backflow Prevention Assemblies — Section 10 of the most current edition of the "Manual of Cross-Connection Control."
2. Said AWWA and USC FCCCHR standards and specifications are adopted by the city of North Las Vegas. Final approval shall be evidenced by a "Certificate of Compliance" for the said AWWA standards; or "Certificate of Approval" for the said USC FCCCHR Specifications; issued by an approved testing laboratory.
3. The following testing laboratory has been qualified by the superintendent of utilities to test and approve backflow prevention assemblies:
Foundation for Cross-Connection Control and Hydraulic Research
University of Southern California
KAP-200 University Park MC-2531
Los Angeles, California 90089-2531
4. Testing laboratories other than the one listed above will be added to the approved list as they are qualified by the manager of utilities operations.
5. Backflow preventers which may be subjected to backpressure or backsiphonage that have been fully tested and have been granted a certificate of approval by said qualified laboratory and are listed on the laboratory's current list of approved backflow prevention assemblies may be used without further test or qualification.
F. It is the duty of the customer at any premise where backflow prevention assemblies are installed to have a field test performed by a properly certified backflow prevention assembly tester upon installation and at least once per year thereafter. In those instances where the manager of utilities operations deems the hazard to be great enough he may require field tests at more frequent intervals. These tests shall be at the expense of the customer and, at the city's option, shall be performed by city personnel or by a certified tester approved by the manager of utilities operations. It shall be the duty of the manager of utilities operations to see that these tests are made in a timely manner. The customer shall notify the manager of utilities operations in advance when the tests are to be undertaken so that an official representative may witness the field tests if so desired. These assemblies shall be repaired, overhauled or replaced at the expense of the customer whenever said assemblies are found to be defective. Records of such tests, repairs and overhauls shall be kept and made available to the manager of utilities operations.
G. All presently installed backflow prevention assemblies which do not meet the requirements of this section, but were approved devices for the purposes described herein at the time of installation and which have been properly maintained, shall, except for the testing and maintenance requirements under subsection F of this section, be excluded from the requirements of these rules so long as the manager of utilities operations is assured that they will satisfactorily protect the city's water system. Whenever the existing device is moved from its present location or requires more than minimum maintenance or when the manager of utilities operations finds that the maintenance constitutes a hazard to health, the unit shall be replaced by an approved backflow prevention assembly meeting the requirements of this section.
H. The director of utilities is authorized to make all necessary and reasonable changes or additions to the city municipal water district service rules and regulations with respect to the enforcement of this chapter. All such rules and policies shall be consistent with the provisions of this chapter and shall be effective immediately upon modification of said service rules and regulations.
(Ord. 1974 § 3, 2004: Ord. 1125 § 2 (part), 1994: prior code § 4.17.030)
Source: City of North Las Vegas, Nevada, Municipal Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/nv/north_las_vegas/codes/code_of_ordinances?nodeId=TIT13PUSE_CH13.20BACRNN_13.20.060POFetched: 11/1/2026