For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

MC 802 — Vents

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Mechanical Code § MC 802

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/db15d9cb-7560-43ca-a1b0-f383fb066381

Section MC 802: Vents

802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. Table 802.2 Vent Application Vent Types Appliance Types Type L oil vents Oil-burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer's instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory-built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code. 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21. 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer's instructions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accordance with their listings and the manufacturer's instructions. 802.7 Support of vents. All portions of vents shall be installed in accordance with the manufacturer's instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than No. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer's instructions. Where vents pass through attic space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer's instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clearance.

Ask a question about New York law

Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.