10-10-2. - Adoption of the International Plumbing Code With Modifications.

(a) The 2024 edition of the International Plumbing Code, published by the International Code Council, including Appendix E, "Sizing of Water Piping System," is hereby adopted by reference as the City of Boulder Plumbing Code or plumbing code, and has the same force and effect as though fully set forth in this chapter, except as specifically amended by the provisions of this chapter. (b) Except for Sections 101, 102, and 107, Chapter 1 is repealed. This code shall be administered in accordance with Chapter 1, "Administration," of the International Building Code as adopted, with amendments, by Section 10-5-2, "Adoption of International Building Code With Modifications," B.R.C. 1981. (c) Section 101.1, "Title," is repealed and reenacted to read: 101.1 Title. These regulations shall be known as the Plumbing Code for the City of Boulder or plumbing code and will be referenced herein as "this code." (d) The Exception to Section 301.3, "Connections to drainage system," is deleted in its entirety. (e) Section 312.5, "Water supply system test," is amended by deleting the words "for piping systems other than plastic" and by modifying the test pressure required from 50 psi (344 kPa) to 100 psi (688 kPa). (f) Section 403.2 Separate Facilities is amended to add the following Exception 5. 5. Separate facilities are not required when multiple fixture all gender facilities are provided. Multiple fixture all gender facilities are not required; they are an alternative to be determined by the property owner or the owners' agent. (g) Section 403.4 "Signage" is repealed and reenacted to read: 403.4 Signage. Required public facilities shall be provided with signs that designate which genders the facility accommodates as required by Section 2902.2. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with Section 1111. Exception: Toilet facilities with only one water closet shall not be identified for exclusive use by any gender and shall be deemed to meet the requirements of this section. Signage shall be provided in accordance with the requirements of the City of Boulder Building Code. (h) Section 403.4.1 Directional signage. Directional signage indicating the route to the required public toilet facilities shall be posted in a lobby, corridor, aisle or similar space, such that the sign can be readily seen from the main entrance to the building or tenant space. (i) Section 403.4.2 All gender signage. Single-user toilet facilities provided in accordance with Section 403.1.2, and family or assisted-use toilet facilities provided in accordance with Section 403.2.1, shall be provided with signs which clearly indicate the facilities are available for use by all genders. (j) Section 403.4.2.1 Existing single-user toilet facilities. After December 31, 2020, all existing single-user toilet facilities and family or assisted-use toilet facilities, shall be provided with signage in accordance with Section 403.4.2. (k) TABLE 404.4 Maximum Flow Rates and Consumption for Plumbing Fixtures and Fixture Fittings," is repealed and reenacted to read: TABLE 404.4 MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES AND FIXTURE FITTINGS

| | | | --- | --- | | PLUMBING FIXTURE OR FIXTURE FITTING | MAXIMUM FLOW RATE OR QUANTITY | | Lavatory, private | 1.5 gpm at 60 psi | | Lavatory, public (metering) | 0.25 gallon per metering cycle | | Lavatory, public (no metering) | 0.5 gpm at 60 psi | | Shower head | 2.0 gpm at 80 psi | | Sink Faucet | 1.5 gpm at 60 psi | | Urinal | 1.0 gallon per flushing cycle | | Water Closet | 1.28 gallons per flushing cycle |

For SI: 1 gallon = 3.785L, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa. a. A handheld shower spray is a shower head. b. Consumption tolerances shall be determined from referenced standards. (l) Section 605.3 is amended by adding a new paragraph to read: Water service line pipe between the water meter and building shall be Type K copper if it is in the public right-of-way, a public utility easement, or on other public property. (m) Section 610, "Disinfection of potable water system," is repealed. (n) Section 712.4.2, "Capacity," is amended by the addition of a new sentence to read: Sewage pumps and sewage ejectors serving public fixtures shall be provided with dual pumps and ejectors arranged to operate independently in case of overload or failure. (o) Section 903.1, "Vent Terminal Required," is repealed and reenacted to read: 903.1 Vent Terminal Required. Open vent pipes that extend through a roof shall be terminated not less than 6 inches above the roof. (p) The Exception to Section 1003.4 is repealed and reenacted to read: Exception: For elevators without firefighter's emergency operation, an oil separator is not required for drainage from hydraulic elevator pits where an approved oil sensing system is installed. (q) Section 1101.3, "Prohibited drainage," is repealed and reenacted to read: 1101.3 Prohibited drainage. No rain, surface, or subsurface water shall be connected to or discharged into any drainage system, unless first approved by the code official. (r) Section 1106.1, "General," is repealed and reenacted to read: 1106.1 General. The size of the vertical conductors and leaders, building storm drains, building storm sewers, and any horizontal branches of such drains or sewers shall be based on the 100-year hourly rainfall rate of 2.5 inches per hour or other approved local weather data. (s) Chapter 13, "NONPOTABLE WATER SYSTEMS," is deleted in its entirety. (t) Chapter 14, "SUBSURFACE GRAYWATER SOIL ABSORPTION SYSTEMS," is deleted in its entirety. (u) Table E103.3(2), "Load Values Assigned to Fixtures," is amended by the addition of a new sentence to read: For the purpose of determining the largest instantaneous demand required in order to size a water meter, this table is repealed and replaced by Chapter 11-1-35, "Meter Size Requirements," B.R.C. 1981. (v) Table E103.3(3), "Table for Estimating Demand," is amended by the addition of a new sentence to read: For the purpose of determining the largest instantaneous demand required in order to size a water meter, this table is repealed and replaced by Chapter 11-1-35, "Meter Size Requirements," B.R.C. 1981. Ordinance Nos. 4879 (1985); 4984 (1986); 5050 (1987); 5177 (1989); 5493 (1992); 5781 (1996); 6065 (1999); 6065 (1999); 7024 (1999); 7566 (2007); 7925 (2013); 8166 (2017); 8209 (2017); 8366 (2020); 8565 (2023); 8684 (2025)