Minimum emergency venting capacity.
46 C.F.R. § 64.63
in effect(a) The total emergency venting capacity (Q) of the relief devices of an uninsulated MPT must be in accordance with table 1 to § 64.63 or the following formula based upon the pressure relief device operating at a pressure not to exceed the test pressure:
Formula 1 to Paragraph (a)
Where:
Q = Minimum required rate of discharge in cubic feet per minute of free air at standard conditions (60 °F and 14.7 psia).
M = Molecular weight of the product, or 86.7.
T = Temperature, degrees Rankine (460° + temperature in °F of gas at relieving temperature), or 710 °R.
A = Total external surface area of the tank compartment in square feet.
L = Latent heat of the product being vaporized at relieving conditions in Btu per pound, or 144 Btu per pound.
Z = Compressibility factor of the gas at relieving conditions, or 1.0.
C = Constant based on relation of specific heats, equal to 315.
(b) The total emergency venting capacity (Q) of an insulated portable tank may have a reduction if—
(1) It is shown to the Coast Guard that the insulation reduces the heat transmission to the tank;
(2) The present reduction of the emergency venting capacity (Q) is limited to the percent reduction of the heat transmission to the tank or 50 percent, whichever is less; and
(3) The insulation is sheathed.
Table 1 to § 64.63—Minimum Emergency Venting Capacity in Cubic Feet: Free Air/Hour
[14.7 lb/in
2a and 60 °F]
Exposed area
square feet
1
Cubic feet free air
per hour
Exposed area
square feet
1
Cubic feet free air
per hour
2027,600275237,000
3038,500300256,000
4048,600350289,500
5058,600400322,100
6067,700450355,900
7077,000500391,000
8085,500550417,500
9094,800600450,000
100104,000650479,000
120121,000700512,000
140136,200750540,000
160152,100800569,000
180168,200850597,000
200184,000900621,000
225199,000950656,000
250219,5001,000685,000
1 Interpolate for intermediate sizes.