For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 31-95 — IMC CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT - amendments

Scottsdale Revised Code (Supp. No. 80: codified through Ordinance No. 4681, adopted July 1, 2025) · Scottsdale Revised Code § 31-95

Corpus is an independent public-information project, not the official City of Scottsdale website. Stable reference: corpuslaw.us/code/e04e0156-5325-44b3-af15-149f470fb2e0

Sec. 31-95. - IMC CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT - amendments.

Only the following portion of CHAPTER 9, SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT, is amended: (a) Section 928.1, General, is amended by adding item 6 as follows: 6. Have a recirculating water pump system. A maximum of 1.5 gallons per hour per 1,000 cfm of bleed-off water may be discharged to prevent the buildup of sediment. This requirement shall apply to new or replacement evaporative cooling equipment.

(Ord. No. 4550, § 1(Res. No. 12500, § 1(Exh. A)), 9-20-22, eff. 1-1-23)

Ask a question about Scottsdale law

Corpus searches the Scottsdale sections it holds and shows the ones that match, with their citations. Free, no sign-in.