Sec. 49-344. - Water supply system testing.

All water piping shall be tested as applicable to one of the following: (a) All water supply systems and any below grade water piping servicing an exterior water outlet(s): The section or complete system filled with water to 100 psig for 15 minutes with no loss of pressure. When testing a plastic systems, all dead ends shall be relieved of air during the process of filling, whether testing entire systems or in sections. (b) Copper water services larger than one inch used for domestic purposes: Hydrostatic or air pressure test to at least 50 psig above the main pressure for one hour. (c) Ductile iron water services used for domestic purposes: Hydrostatic test to at least 200 psig for one hour. (d) Water services used for fire protection: A hydrostatic test to at least 200 psig for two hours. All water used for testing shall be obtained from a potable source.

(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 4, 8-13-21)