§ 23-7-5(E) — Fire Protection for Piers, Docks, and Wharves

Code of Ordinances, City of Biloxi, Mississippi (Supp. No. 63, Update 1: codified through Ordinance No. 2607, enacted July 28, 2026) · Biloxi Land Development Ordinance § 23-7-5(E)

Corpus is an independent public-information project, not the official City of Biloxi website. Stable reference: corpuslaw.us/code/e286bc5e-d0ca-4975-81db-b7770641e0eb

(E) - Fire Protection for Piers, Docks, and Wharves

Where a standpipe system is required for a pier, dock, or wharf, it shall be provided in accordance with the Standard Fire Prevention Code and NFPA 14 and shall be located as follows: (1) A Fire Department Connection (FDC) to the standpipe system shall be located at the entrance to the pier, dock, or wharf. (2) A gated outlet to the standpipe system shall be located no more than 50 linear feet from the farthest end of the pier, dock, or wharf, and gated outlets to the standpipe system shall be spaced no more than 100 linear feet thereafter for the entire length of a pier, dock, or wharf. (3) Where a pier, dock, or wharf has more than one branch, a standpipe shall be located no more than 50 linear feet from the farthest end of each branch of the pier, dock, or wharf, and gated connections to the standpipe system shall be spaced no more than 100 linear feet thereafter for the entire length of a pier, dock or wharf.