Pretreatment standards for new sources.
40 C.F.R. § 428.76
in effectAny new source subject to this subpart that introduces process wastewater pollutants into a publicly owned treatment works must comply with 40 CFR part 403, in addition to the limitations set forth in paragraphs (a) and (b) of this section.
(a) The following pretreatment standard establishes the quantity or quality of pollutants or pollutant properties, controlled by this section, which may be discharged to a publicly owned treatment works by a new point source subject to the provisions of this subpart:
Pollutant or pollutant property
Pretreatment standard
pHNo limitation.
TSS Do.
Oil and grease100 mg/l daily maximum.
(b) The following pretreatment standard establishes the quantity or quality of pollutants or pollutant properties controlled by this section, and attributable to lead-sheathed hose production, which may be discharged to a publicly owned treatment works by a new point source subject to the provisions of this subpart, in addition to the limitations set forth by § 428.76(a):
Effluent characteristic
Effluent limitations
Maximum for any 1 day
Average of daily values for 30 consecutive days shall not exceed—
Metric units (kg/kkg of raw material)
Lead0.00170.0007
English units (lb/1,000 lb of raw material)
Lead0.00170.0007