Sec. 44-1241. - Standards for development in the coastal floodplain district.
Development in the CFD shall meet the requirements of Division 4, as well as all of the following requirements.
(1) New construction shall be located landward of the ordinary high water mark.
(2) Bulkheads, seawalls, revetments, and other erosion control measures shall not be connected to the foundation or superstructure of a building and shall be designed and constructed so as not to direct floodwaters or increase flood forces or erosion impacts on the foundation or superstructure of any building.
(3) Human-made alterations of sand dunes are prohibited unless an engineering report documents that the alterations will not increase potential flood damage by reducing the wave and flow dissipation characteristics of the sand dunes.
(4) The use of fill for structural support of buildings is prohibited.
a. Non-structural fill shall be permitted only if an engineering report demonstrates that the fill will not cause runup, ramping, or deflection of floodwaters that cause damage to buildings.
(5) New construction and substantial improvement of buildings shall be elevated, consistent with Wis. Admin. Code SPS § 321.34, on pilings or columns so that the bottom of the lowest horizontal structural member of the lowest floor (excluding the pilings or columns) is elevated to or above the FPE.
a. The pile or column foundation and structure attached thereto shall be anchored to resist flotation, collapse, and lateral movement due to the effects of wind and water loads acting simultaneously on all building components. Water loading values shall be those associated with the base flood. Wind loading values shall be those defined according to American Society of Civil Engineers 7-16 Minimum design loads and associated criteria for buildings and other structures or other equivalent standard.
b. A registered professional engineer or architect shall develop or review the structural design, specifications, and plans for the construction and shall certify that the design and methods of construction to be used are in accordance with accepted standards of practice for meeting the provisions of Section 44-1241(5).
(6) New construction and substantial improvement of buildings shall have the space below the lowest floor either free of obstruction or constructed with non-supporting breakaway walls, open wood lattice-work, or insect screening intended to collapse without causing collapse, displacement, or other structural damage to the elevated portion of the building or supporting foundation system.
a. For the purpose of Section 44-1241(6), a breakaway wall shall have a design safe loading resistance of not less than ten and not more than 20 pounds per square foot.
b. Use of breakaway walls which exceed a design safe loading resistance of 20 pounds per square foot, either by design or where so required by local or state codes, may be permitted only if a registered professional engineer or architect certifies that the designs proposed meet all of the following conditions.
1. Breakaway wall collapse shall result from a water load less than that which would occur during the base flood; and
2. The elevated portion of the building and supporting foundation system shall not be subject to collapse, displacement, or other structural damage due to the effects of wind and water loads acting simultaneously on all building components (structural and non-structural). Water loading values shall be those associated with the base flood. Wind loading values shall be those defined according to American Society of Civil Engineers 7-16 Minimum design loads and associated criteria for buildings and other structures, or equivalent standard.
c. All space enclosed by breakaway walls, open wood lattice-work, or insect screening below the lowest floor shall be used solely for parking, building access, or storage.
(7) Require within flood-prone areas:
a. New and replacement water supply systems to be designed to minimize or eliminate infiltration of flood waters into the systems; and
b. New and replacement sanitary sewage systems to be designed to minimize or eliminate infiltration of flood waters into the systems, discharges from the systems into flood waters, and onsite waste disposal systems to be located to avoid impairment to them or contamination from them during flooding.
(8) All mobile recreation vehicles must be on site for fewer than 180 consecutive days and satisfy one of the following requirements.
a. The vehicle must be fully licensed and ready for highway use.
b. The vehicle must meet the standards of Section 44-1241(1) through (9), inclusive.
(9) Manufactured homes placed or substantially improved within the Coastal Floodplain District shall meet the standards of Section 44-1241(1) through (9), inclusive.
(Ord. No. 05-23, § 1, 3-21-2023)