Corpus Christi Code of Ordinances § 14-261 Fuel gas code.
Sec. 14-261. - Fuel gas code.
The International Fuel Gas Code, 2021 Edition, as published by the International Code Council, is incorporated by reference and adopted as the Fuel Gas Code for the City of Corpus Christi with the following local amendments (Additions to the International Fuel Gas are shown as underlined text. Deletions to the International Fuel Gas Code are shown as strikethroughs):
101.1 Title. These regulations shall be known as the Fuel Gas Code of the City of Corpus Christi, hereinafter referred to as "this code."
101.3 Appendices. Appendix A, Sizing and Capacities of Gas Piping; Appendix B, Sizing of Venting Systems Serving Appliances Equipped with Draft Hoods, Category I Appliances and Appliances Listed for Use with Type B Vents; Appendix C, Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems; and Appendix D, Recommended Procedure for Safety Inspection of an Existing Appliance Installation.
103.1 Creation of agency. The City of Corpus Christi Development Services Department is hereby created named and the official in charge thereof shall be known as the code official. The function of the agency shall be the implementation, administration and enforcement of the provisions of this code.
109.2 Schedule of permit fees. Where work requires a permit, a fee for each permit shall be paid as required, in accordance with the schedule as established by the applicable governing authority. Reference the City of Corpus Christi fee schedule.
Section 113 of the International Fuel Gas Code is deleted. Refer to Section 14-206(a) Construction Trade Advisory Appeal Board for details on the establishment, duties and powers, and appeals process of the construction trade advisory & appeals board.
Section 114 of the International Fuel Gas Code is deleted. Refer to Section 14-206(a) Construction Trade Advisory Appeal Board for details on the establishment, duties and powers, and appeals process of the construction trade advisory & appeals board.
Section 115 of the International Fuel Gas Code is deleted. Refer to Section 14-207 Violations and Penalties.
404.1.2 Prohibited fittings. All threaded bushings shall be prohibited.
404.12 Minimum burial depth. Underground piping systems shall be installed at a minimum depth of 12 inches (305 mm) eighteen (18) inches (257 mm) below grade, except as provided for in Section 404.12.1. If a minimum of eighteen (18) inches (257 mm) of cover cannot be maintained, the pipe must be installed in conduit or bridged (shielded).
406.4 Test pressure measurement. Test pressure shall be measured with a manometer or with a pressure measuring device designed and calibrated to read, record, or indicate a pressure loss due to leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five time the test pressure.
Exception: A spring-type mechanical gauge may not be used.
(Ord. No. 030847, 5-17-2016; Ord. No. 032058, § 14, 3-17-2020; Ord. No. 032968, § 5, 1-31-2023)