§ 22-7-6 — Testing of backflow prevention devices

Code of Ordinances, City of Biloxi, Mississippi (Supp. No. 63, Update 1: codified through Ordinance No. 2607, enacted July 28, 2026) · Biloxi Code of Ordinances § 22-7-6

Corpus is an independent public-information project, not the official City of Biloxi website. Stable reference: corpuslaw.us/code/e5666871-9cfc-4470-971f-016ad627f41a

Sec. 22-7-6. - Testing of backflow prevention devices.

(a) Right to enter. The department shall have the right to enter any nonresidential building, during reasonable hours, to inspect the plumbing system installed in any such building or premises provided prior notification of the inspection is given. The department shall first obtain consent of the owner to enter any residential dwelling. (b) Tests required. Each reduced pressure principal backflow prevention assembly, double check valve assembly, and pressure vacuum breaker installed shall be tested after installation, after repairs of any kind, and annually. Any backflow preventer found to be nonfunctional shall be repaired and retested within 14 days of the initial test. (c) Certified testers. Only backflow preventer testers certified by the department of health shall test backflow preventers located in the city. (d) Repairs and replacements. Any backflow preventer which fails during a periodic test will be repaired or replaced. When repairs are necessary, upon completion of the repair the device will be retested at owner's expense to insure correct operation. High hazard situations will not be allowed to continue unprotected if the backflow preventer fails the test and cannot be repaired immediately. In other situations, a compliance date of not more than 14 days after the test date will be established. The owner is responsible for spare parts, repair tools, or a replacement device. Parallel installation of two devices is an effective means of the owner insuring that uninterrupted water service during testing or repair of devices and is strongly recommended. (Ref. Fig. 33, Exhibit "A.") (e) Additional testing. Backflow prevention devices will be tested more frequently than specified in subsection (b) above, in cases where there is a history of test failures and the department feels that due to the degree of hazard involved, additional testing is warranted. Cost of the additional tests will be borne by the owner. (f) Notification of testing. The department shall notify the owner of each backflow preventer 60 days prior to the date that the backflow preventer is scheduled to be tested.

(Ord. No. 1889, § 1, 8-3-99; Ord. No. 1901, § 1, 9-28-99)

Ask a question about Biloxi law

Corpus searches the Biloxi sections it holds and shows the ones that match, with their citations. Free, no sign-in.