Water distribution system.
Houston Code of Ordinances § 29-99
in effectSec. 29-99. - Water distribution system.
(a) All water piping, fixtures and other equipment shall be constructed and maintained in accordance with state and local regulations and requirements and shall be of a type and in locations approved by the city.
(b) The water piping system shall not be connected with nonpotable or questionable water supplies and shall be protected against the hazards of backflow or back siphonage.
(c) The system shall be so designed and maintained as to provide a pressure of not less than 20 pounds and not more than 80 pounds per square inch, under all normal operating conditions at each manufactured home stand. Also, the system shall be capable of supplying, e.g., 50 manufactured homes with a demand load of 100 gpm, 100 manufactured homes with 180 gpm, and 300 manufactured homes with 370 gpm. Greater design values will be required when the system is to provide fire hydrants. In such event, the water supply system shall permit the operation of a minimum of two 1½-inch hose streams, and the system shall deliver at least 250 gallons of water per minute for fire-fighting purposes.
(d) In any manufactured home park where recreational vehicles are permitted there shall be one or more water supply outlets for filling recreational vehicles water storage tanks. At least one such water supply outlet shall be easily accessible to any lot used by a recreational vehicle. Such water supply outlets shall consist of at least a water hydrant and the necessary appurtenances and shall be protected against the hazards of backflow and back siphonage. Such watering station shall be designed and maintained so that there is no accumulation of any water spillage on the water station site.
(e) All manufactured homes and buildings proposed to be constructed or placed within a manufactured home park containing private streets must be so arranged and located that fire-fighting apparatus can park and reach any part of any building and any manufactured home with a two hundred-foot long hose extending from such equipment. This two hundred-foot hose length must be measured as the hose is laid on the ground and may not be measured as an aerial radius from such parked equipment. In addition, fire hydrants must be so located and provided within the project boundaries so that 500 feet of fire hose, extending on the ground from the hydrant, can reach the furthermost part of any building and manufactured home within the boundaries of the park. The 500 feet includes the 200 feet of hose from the fire-fighting apparatus to the building or manufactured home and 300 feet of hose from the fire hydrant to the apparatus along the private street. Therefore, the distance between fire hydrants located along the private street shall not exceed 600 feet to ensure adequate fire protection. Entrances to all buildings and manufactured homes must be illustrated on the plat of any project containing private streets.
(f) Water mains, if installed parallel to sewer lines, shall be separated by ten feet horizontally from any sanitary sewer, storm sewer or sewer manhole, unless alternate methods of installation are approved.
(Ord. No. 85-498, § 1, 4-10-85)