Sec. 591-404. - Requirements for commercial kitchen exhaust equipment and fire protection equipment.

Any new installation of kitchen fire suppression equipment shall be inspected by the fire prevention bureau having jurisdiction prior to the kitchen cooking equipment being placed in-service. The installing company shall: (1) Use installers that are certified by the manufacturer; (2) Notify the fire prevention bureau at least twenty-four (24) hours in advance of the system being completed for system testing; and, (3) File with the fire prevention bureau a form stating that the system has been inspected, signed by both the fire prevention inspector and the installation company's representative. This form is to be kept on file in the fire prevention bureau.

(G.O. 43, 2002, § 2)