High hazard.
Charlotte City Code § 23-174
in effectSec. 23-174. - High hazard.
(a) The activities set forth in this section are a high hazard and require the use of the specified backflow-prevention assembly.
(b) If a tank or a reservoir is filled in whole or in part by water from the public water system, an approved air-gap separation must be installed unless CMU authorizes the installation of an approved reduced-pressure principle assembly in lieu of an approved air-gap separation. Before a private water system which is connected in any manner to the public water system may receive water from an auxiliary water supply, an approved air-gap separation must be installed between the auxiliary water supply and the private water system.
(c) An approved reduced-pressure principle assembly must be installed if the private water system is served in any manner by an auxiliary water supply or if the private water system is subject in any manner to contamination by any means as a result of the activities or processes associated with the use of the private water system. Following is a list of facilities, activities or processes which include, but are not limited to, conditions requiring the installation of an approved reduced-pressure principle assembly:
(1) Any private water system used or designed for use with a booster pump or which may become pressurized for any reason to the extent that backpressure may occur.
(2) Any private water system which contains water which has been or is being recirculated.
(3) A private water system, any portion of which is elevated more than 50 feet above any service connection between such private water system and the public water system.
(4) Bottling plant, brewery.
(5) Carwash with recycling system.
(6) Chemical plant.
(7) Dentist's office.
(8) Dry cleaning plant.
(9) Exterminating company.
(10) Fertilizer plant.
(11) Film laboratory.
(12) Fire sprinkler system or standpipe system with any one or more of the following: chemical additive, booster pump or fire department connection (FDC).
(13) Hospital, clinic, medical building.
(14) Irrigation system, with or without chemical additives.
(15) Laboratory.
(16) Commercial laundry, except self-service laundry.
(17) Metal processing plant.
(18) Morgue or mortuary.
(19) Nursing home.
(20) Pharmaceutical plant.
(21) Power plant.
(22) Swimming pool.
(23) Sewage treatment plant.
(24) Tire manufacturer.
(25) Veterinary hospital, clinic, office.
(d) An approved reduced-pressure principle assembly must be installed under any of the following circumstances:
(1) CMU does not have sufficient access to every portion of a private water system to permit the complete evaluation of the degree of hazard associated with such private water system;
(2) The use of the premises containing a private water system is not known; or
(3) The premises containing a private water system is used by two or more nonresidential tenants.
(Code 1985, § 23-103; Ord. No. 2269, § 1, 3-24-2003; Ord. No. 5006, §§ 2, 3, 11-26-2012)