Sec. 49-1121. - Inspection manhole.
The inspection manhole shall allow for proper inspection, sampling, temperature monitoring and flow measurement of the building sewer. The following provisions shall also apply: (a) Shall be required when the capacity of the interceptor for a non-certified interceptor is greater than 1,500 gallons or 1,000 gallons for a certified interceptor. (b) All building wastewater shall flow through the inspection manhole. (c) Two distinct discharge lines, one containing domestic discharge and the other originating from the interceptor, shall discharge separately into the inspection manhole. (d) Shall be installed on the user's premises. (e) Shall be designed to allow traffic loading. (f) Shall be a minimum 72 inches inside diameter. (g) There shall be a minimum distance between the interceptor and the manhole of 20 times the size of the pipe with no fittings.
(Ord. No. 40524, § 1, 10-20-15)