Sec. 49-1525. - Location and protection of post indicator value (PIV).

(a) Location. (1) Post indicator valves shall be located not less than 40 feet from the building. (2) Where the post indicator valve cannot be located more than 40 feet then with permission by the authority having jurisdiction the post indicator valve may be located closer. (3) The top of the post indicator valve shall be set so the top of the post is 36 inches above the final grade. (b) Protection. (1) Six-inch schedule 40 steel bollards are required when the PIV is less than six feet back of a curb or drive except as noted in subsection (2). (2) Eight-inch schedule 40 steel bollards will be require in the following: (i) When located on the north side of the building located on a street that slopes more than three percent. (ii) When installed in a parking lot or truck delivery lanes and dock areas. (3) When installed on a slope the 36 inches measurement from ground level to the top of the nut will be taken from the center line of the PIV. (4) The hole for the bollard shall be eight inches larger than the outside diameter of the pipe. The pipe shall centered in the hole and the hole filled with concrete. (i) The concrete shall be 3,000 pound rated. (ii) The pipe shall be filled with concrete. See Figure 49-1525 and Figure 49-1560.

(Ord. No. 42654, § 46, 8-13-21)

Ask a question about Omaha law

Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.