§ 15.32.020 — Amendments, Additions, and Omissions
Municipal Code of the City of Shawnee, Kansas (Codified through Ordinance No. 3558, adopted August 10, 2026. (Supp. No. 9, Update 2)) · Shawnee Municipal Code § 15.32.020
Corpus is an independent public-information project, not the official City of Shawnee website. Stable reference: corpuslaw.us/code/f1603409-5dfa-46b8-af17-f69b1c52cd0c
15.32.020 - Amendments, Additions, and Omissions.
The following Sections of the IFC, as adopted by Section 15.32.010, are amended or omitted as follows: A. Amend Section 101.1 Title, of the IFC by replacing "[NAME OF JURISDICTION]" with "City of Shawnee, Kansas." B. Amend Section 101.2.1 Appendices, of the IFC, and amend by adding in lieu thereof a new Section 101.2.1 Appendices, which reads: Section 101.2.1 Appendices. Provisions in the appendices shall not apply unless specifically adopted. The following appendices are adopted in this code. Appendices A, B, C, D, H, I, and O C. Amend Section 102 Applicability, of the IFC, and amend by adding in lieu thereof a new Section 102.13 Home daycares, which reads: Section 102.13 Home daycares. Home Daycares that meet the requirements of the most current edition of the Johnson County, Kansas Home Daycare Handbook shall be viewed as meeting the equivalent of the requirements of the IFC. D. Amend Section 103.1 Creation of agency, of the IFC, and amend by adding in lieu thereof a new Section 103.1 Creation of agency, which reads: Section 103.1 Creation of agency. The City of Shawnee Fire Department Community Risk Reduction Division is hereby created and the official in charge thereof shall be known as the fire code official. The function of the agency shall be the implementation, administration, and enforcement of the provisions of this code. E. Amend Section 103.2 Appointment, of the IFC, and amend by adding in lieu thereof a new Section 103.2 Appointment, which reads: Section 103.2 Appointment. The fire code official shall be appointed by the chief appointing authority of the jurisdiction; and the fire code official shall not be removed from office except for cause and after full opportunity to be heard on specific and relevant charges by and before the appointing authority. F. Omit Sections 105.5.1 through 105.5.6, Sections 105.5.8 through 105.5.13, Section 105.5.15, Sections 105.5.17 through 105.5.21, Sections 105.5.27 through 105.5.28, Sections 105.5.30 through 105.5.33, Section 105.5.35, and Sections 105.5.37 through 105.5.57 of the IFC. G. Amend Section 105.5.22 Hazardous materials, of the IFC, and amend by adding in lieu thereof a new Section 105.5.22 Hazardous Materials, which reads: Section 105.5.22 Hazardous materials. An operational permit shall be required for all High-Hazard (Group H) occupancies. As a condition of the permit, the facility shall submit a current Hazardous Materials Management Plan (HMMP) and a Hazardous Materials Inventory Statement (HMIS) at the time of application. Updated HMMP and HMIS documents shall be submitted annually or whenever changes occur from the originally submitted documents. H. Amend Section 105.5.34 Mobile food preparation vehicle, of the IFC, and amend by adding in lieu thereof a new Section 105.5.34 Mobile food preparation vehicle, which reads: Section 105.5.34 Mobile food preparation vehicle. A Heart of America Fire Chiefs Association (HOA) operational inspection permit is required for mobile food preparation vehicles equipped with appliances that produce smoke and 1 or grease laden vapors. I. Omit Sections 105.6 through 105.6.25 of the IFC. J. Amend Section [A] 113.4 Violation penalties, of the IFC, and amend by adding in lieu thereof a new Section [A] 113.4 Violation penalties, which reads: Section [A] 113.4 Violation penalties. Any person who violates a provision of this Code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the fire code official, or of a permit or certificate issued under the provisions of this Code, shall be guilty of a public offense, and upon conviction shall be subject to penalties as set forth in Title 15 of the Shawnee Municipal Code. Each day that a violation continues shall be deemed a separate offense. K. Amend Section 202 Definitions of the IFC, and amend by adding the following definitions: ELECTRIC VEHICLE (EV) An over-the-road automotive-type vehicle for highway use, such as a passenger automobile, bus, truck, van or similar vehicle, which receives primary or supplementary power from an electric motor that draws current from a rechargeable battery. This term is used to cover electric vehicles, hybrid electric vehicles, and plug-in versions of these vehicles. ELECTRIC VEHICLE CHARGING STATION (EVCS) A public or private parking space that is served by battery charging station equipment, including any electrical component, assembly, or cluster of component assemblies, that is designed to, or has a primary purpose of, the transfer of electric energy (by conductive or inductive means) to a battery or other energy storage device in an electric vehicle. LEVEL 1 ELECTRIC VEHICLE CHARGING STATION An electric vehicle charging station that operates on a 15-to-20-amp breaker on a 120- volt AC circuit. LEVEL 2 ELECTRIC VEHICLE CHARGING STATION An electric vehicle charging station that operates on a 220- or 240-volt AC circuit. LEVEL 3 ELECTRIC VEHICLE CHARGING STATION An electric vehicle charging station that operates on greater than 240-volt circuit with special grounding equipment. Level 3 stations can also be referred to as rapid charging stations that are typically characterized by industrial grade electrical outputs that allow for faster recharging of electric vehicles. SURFACE PARKING LOT Parking which is not enclosed or created by a structure and is an area at grade, or on ground level. STRUCTURED PARKING LOT Parking which is an above-grade, ramp access, open or enclosed parking garage structure specifically designed to accommodate vehicle parking or on-grade parking that is sheltered under a building that is elevated on piers. L. Amend Section 307.4.3 Portable outdoor fireplaces of the IFC, and amend by adding in lieu thereof a new Section 307.4.3 Portable outdoor fireplaces, which reads: Section 307.4.3 Portable outdoor fireplaces. Portable outdoor fireplaces shall not be operated or located within 15 feet (3048 mm) of combustible construction. Exceptions: One-and-two family dwellings. M. Amend Chapter 3 General Requirements of the IFC, and amend by adding a new Section 323 - Electric Vehicle Charging Stations. N. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.1 General, which reads: Section 323.1 General. All electric vehicle charging stations (EVCS) shall adhere to Section 323 - Electric Vehicle Charging Systems. O. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.2 General requirements, which reads: Section 323.2 General requirements. 1. Electric vehicle charging stations (ECVS) shall be installed in accordance with NFPA 70. 2. Electric vehicle charging equipment shall be listed and labeled in accordance with UL 2202 and Section 406.2.7 of the IBC. 3. Electric supply equipment shall be listed and labeled in accordance with UL 2594. P. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.3 Fire Protection Requirements, which reads: Section 323.3 Fire Protection Requirements Q. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.3.1 Technical opinion report, which reads: Section 323.3.1 Technical opinion report. A technical opinion report, complying with Section 104.2.2, shall be prepared to evaluate the fire and explosion risks associated with the electric vehicle charging stations and to make recommendations for fire and explosion protection. The report shall be sealed by a registered Kansas design professional and submitted to the fire code official for approval. In addition to the requirements of section 104.2.2, the technical opinion and report shall specifically evaluate the following: 1. The potential for deflagration of flammable gasses releases during an electric vehicle thermal runaway event. 2. The basis of design for an automatic sprinkler system. Such design basis shall reference appropriate NFPA standards and relevant full-scale fire testing or another approved method of demonstrating sufficiency of the recommended design. R. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.3.2 Standpipe Systems, which reads: Section 323.3.2 Standpipe systems. All parking structures with two or more tiers with Level 2 and Level 3 electric vehicle charging stations shall be provided with a class-1 standpipe system, in accordance with Section 905.3.8, and shall be in an approved location not less than 20 feet and no more than 100 feet from electric vehicle charging systems. S. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.3.3 Surface Parking Fire Hydrants, which reads: Section 323.3.3 Surface parking fire hydrants. Where Level 2 or Level 3 electric vehicle charging stations are installed on a surface parking lot, fire hydrant placement shall comply with Section 507.5. T. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.4 Placement of Vehicle Charging Stations, which reads: Section 323.4 Placement of Vehicle Charging Stations. U. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.4.1 Prohibited locations, which reads: Section 323.4.1 Prohibited locations. A Level 3 electric vehicle charging station shall not be installed inside or under any structure or buildings, nor inside, under, or on top of any parking garage or parking structure. Exception: When the top level of the parking structure is on or at street level on one entire side of the structure, the top level shall be treated as a surface parking lot. V. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.4.2 Parking structure distance from electric vehicle charging stations to exposures, which reads: 323.4.2 Surface parking lot distances from electric vehicle charging stations to exposures. In a surface parking lot, the entirety of an electric vehicle charging station providing a Level 2 or Level 3 charge, including the vehicle parking space area, shall be separated from the following materials and structures by the defines distance: Item | Distance (ft) Means of Ingress/Egress or Emergency Exit Pathway | 50 Buildings/Structures/Property lines | 25 Utility Poles | 25 Utility Distribution Infrastructure deemed to Pose a Potential Public Safety Hazard | 25 Fuel Tank or Gas Pump | 50 Electrical Meters, Gas Meters, or Gas Pipes | 25 Trees | 10 Ground Vegetation or Mulching | 15 W. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.4.3 Structured parking lot distances from electric vehicle charging stations to exposures, which reads: 323.4.3 Structured parking lot distances from electric vehicle charging stations to exposures. In a structured parking lot, the entirety of an electrical vehicle charging station providing a Level 2 charge, including the vehicle parking space area, shall be separated from the following materials and structures by the defined distances: Item | Distance (ft) Means of Ingress/Egress or Emergency Exit Pathway | 50 Buildings/Structures/Property lines | 25 Utility Poles | 25 Utility Distribution Infrastructure deemed to Pose a Potential Public Safety Hazard | 25 Fuel Tank, Gas Pump or UST/AST Refueling Operations | 50 X. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.5 Installation requirements, which reads: Section 323.5 Installation Requirements. Y. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.5.1 Required signage, which reads: 323.5.1 Required signage. All Level 2 and Level 3 electric vehicle charging stations shall include the following information signage as a minimum for fire department response: voltage and amperage levels and contact information for reporting when the electric vehicle charging station is not operating or other problems with the station. Z. Amend Section 323-Electric Vehicle Charging Stations of the IFC, and amend by adding a new Section 323.5.3 Emergency disconnect, which reads: 323.5.3 Emergency disconnect. An emergency disconnect that is approved by the fire code official, shall be installed per the locally amended Section 625.43 of the National Electrical Code (NEC). The emergency disconnect switch shall contain a readily legible sign that reads: "Electric Vehicle Emergency Disconnect." Exceptions: One- and Two- family dwellings. AA. Amend Section 503.3 Marking, of the IFC, and amend by adding in lieu thereof a new Section 503.3 Marking, which reads: Section 503.3 Markings. Where required by the fire code official, approved signs and painted curb, or pavement if curb is absent, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. The curb, or pavement if curb is absent, shall be painted red with white 3-inch letters indicating "NO PARKING FIRE LANE". Lettering shall occur every 25 feet of the fire lane. Signs used to indicate fire lanes shall meet the requirements of section D103.6 of the 2024 International Fire Code. BB. Amend Section 503.6 Security gates, of the IFC, and amend by adding in lieu thereof a new Section 503.6 Security gates, which reads: 503.6 Security gates. The installation of security gates across a fire department access road shall be approved by the fire code official. Where security gates are installed, they shall have an approved means of emergency operation with a secondary means of operation in the event of failure of the primary operation. The security gates and emergency operation shall be maintained operational at all times. Electric gate operators, where provided, shall be listed in accordance with UL 325. Gates intended for automatic operation shall be designed, constructed, and installed to comply with the requirements of ASTM F2200. CC. Amend Section 503 of the IFC, and amend by adding in lieu thereof a new Section 503.6.1 Emergency access, which reads: 503.6.1 Emergency access. All security/access control gates shall be provided with a manual means of operating the gate and an automatic means of operation. The automatic means of operation shall be accomplished with an Opticom, or a Knox Box KS-2 switch. DD. Amend Section 507.5.1.1 Hydrant for standpipe systems, of the IFC, and amend by adding in lieu thereof a new Section 507.5.1.1 Hydrant for standpipe systems, which reads: 507.5.1.1 Hydrant for fire sprinkler and standpipe systems. Buildings equipped with a fire sprinkler or standpipe systems, that are installed in accordance with Section 903 or 905, shall have a fire hydrant within 100 feet of the fire department connections. EE. Amend Section 507, of the IFC, and amend by adding in lieu thereof a new Section 507.5.2.1 Line and hydrants tests, which reads: Section 507.5.2.1 Line and hydrant tests. Private hydrants and supply piping shall be tested as specified in NFPA 24. Hydrants shall comply with the AWWA standards adopted by the Johnson County Water District and maintained to AWWA-M17. FF. Amend Section 507, of the IFC, and amend by adding in lieu thereof a new Section 507.5.2.2 Private hydrant color, which reads: 507.5.2.2 Private Hydrant - color. All fire hydrants shall be painted red in color and be highly visible. GG. Amend Section 903.3.8.5 Calculations, of the IFC, and amend by adding in lieu thereof a new Section 903.3.8.5 Calculations, which reads: Section 903.3.8.5 Calculations. Hydraulic calculations in accordance with NFPA 13 shall be provided to demonstrate that the available water flow and pressure are adequate to supply all sprinklers installed in any single fire area with discharge densities corresponding to the hazard classification. Calculations shall have a minimum safety factor of 5 psi. When calculating the water supply requirements for new installations, the minimum safety factor shall be deducted from the actual static and residual pressure. The actual flow calculation and minimum safety factor reduction calculation shall be shown on the hydraulic calculation sheets Exception: NFPA 13D systems (one and two-family dwellings). HH. Amend Section 906.1 Where required, of the IFC, and amend by adding in lieu thereof a new Section 906.1 Where required, which reads: 906.1 Where required. Portable fire extinguishers shall be installed in the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exceptions: In Group E occupancies, portable fire extinguishers shall be required only in locations in specified in Items 3 through 7 where each classroom is provided with a portable fire extinguisher having a minimum rating of 2-A:20-B:C. 2. In storage areas of Group S occupancies where forklift, powered industrial truck or powered cart operators are the primary occupants, fixed extinguishers, as specified in NFPA 10, shall not be required where in accordance with all of the following: 2.1 Use of vehicle-mounted extinguishers shall be approved by the fire code official. 2.2 Each vehicle shall be equipped with a 10-pound, 40A:80B:C extinguisher affixed to the vehicle using a mounting bracket approved by the extinguisher manufacturer or the fire code official for vehicular use. 2.3 Not less than two spare extinguishers of equal or greater rating shall be available on-site to replace a discharged extinguisher. 2.4 Vehicle operators shall be trained in the proper operation, use and inspection of extinguishers. 2.5 Inspections of vehicle-mounted extinguishers shall be performed daily. 3. Within 30 feet (9144mm) distance of travel from commercial cooking equipment and from domestic cooking equipment in Group 1-1; I-2, Condition 1; and R-2 college dormitory occupancies. 4. In areas where flammable or combustible liquids are stored, used or dispensed. 5. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3306.6. 6. Where required by the sections indicated in Table 906.1. 7. Special hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Exception: Portable fire extinguishers are not required at normally unmanned Group U occupancy buildings or structures where a portable fire extinguisher suitable for the hazard of the location is provided on the vehicle of the visiting personnel. II. Omit Section 907.2.7.1.1 Occupant notification, of the IFC. JJ. Amend Section 912.3 Fire hose threads of the IFC, by adding in lieu of a new Section 912.3 Fire hose threads, which reads: Section 912.3 Fire hose threads. Fire hose threads used in connection with fire sprinkler systems and standpipe systems shall be a four-inch (4") Storz quick coupling connector. KK. Omit Chapter 11, of the IFC, except Sections 1103.8 through 1103.9 and 1107.1 through 1107.1.2. LL. Amend Section 4104.2 Open flame cooking devices, of the IFC, and amend by adding in lieu thereof a new Section 4104.2 Portable Fuel Fires Cooking Appliances, which reads: 4104.2 Portable fuel fired cooking appliances. Charcoal burners and other open-flame cooking devices (including pellet grills/smokers and wood burning smokers) shall not be operated or located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an automatic sprinkler system. 3. LP-gas cooking devices having LP-gas container with a water capacity not greater than 2½ pounds [nominal 1 pound (0.454 kg) LP-gas capacity]. MM. Amend Section 5601.2 Permit required, of the IFC, and amend by adding in lieu thereof a new Section 5601.2 Permit required, which reads: 5601.2 Permit required. A permit application shall be made to the City of Shawnee fire department who shall issue the same only if the Fire Chief or their designated representative shall after inspection approve issuance of the permit. The application fee shall be approved by the Governing Body and listed in the latest City of Shawnee Policy Statement (PS-56). Permits shall expire 30 days after date of issuance. Permits shall be obtained: 1. To manufacture, possess, store, sell, display, or otherwise dispose of explosive materials. 2. To use explosive materials. 3. To operate a terminal for handling explosive materials. NN. Amend Section 5601.2.4 Financial responsibility, of the IFC, and amend by adding in lieu thereof a new Section 5601.2.4 Financial responsibility, which reads: Section 5601.2.4 Financial responsibility. Before a permit is issued, as required by Section 5601.2, the applicant shall file with the jurisdiction a corporate surety bond in the principal sum of $1,000,000 or a public liability insurance policy for the same amount, for the purpose of the payment of all damages to persons or property which arise from, or are caused by, the conduct of any act authorized by the permit upon which any judicial judgment results. The fire code official is authorized to specify a greater or lesser amount when, in his or her opinion, conditions at the location of use indicate a greater or lesser amount is required. Government entities shall be exempt from this bond requirement. OO. Amend Section 5601.2.4.2 Fireworks display, of the IFC, and amend by adding in lieu thereof a new Section 5601.2.4.2 Fireworks display, which reads: 5601.2.4.2. Fireworks display - When any person makes application for a permit of supervised public displays of fireworks pursuant to Section 5601.2.4.2 of the International Fire Code 2024 Edition, the applicant shall at the time of filing the application therefore pay to the City Clerk an application fee as outlined in PS-56. The application fee shall be refunded upon request by the applicant in the event the application for such is withdrawn or denied prior to an investigation being made as provided under section of such code; however, no refund shall be made for any reason after the Fire Chief or his designated representative has made the required investigation. PP. Amend Section 5601.4 Qualifications., of the IFC, and amend by adding in lieu thereof a new Section 5601.4 Qualifications, which reads: 5601.4 Qualifications. Persons in charge of magazines, blasting, fireworks display or pyrotechnic special effect operations shall not be under the influence of alcohol or drugs which impair sensory or motor skills, shall be at least 21 years of age and shall demonstrate knowledge of all safety precautions related to the storage, handling or use of explosives, explosive materials or fireworks, possess a valid Blasters Certificate issued by the State of Kansas Fire Marshal's Office, ATF&E Notice of Clearance, and valid photo identification. QQ. Amend by omitting Section 5607.4 Restricted hours, of the IFC, and amend by adding in lieu thereof a new Section 5607.4 Hours of operation, which reads: Section 5607.4 Hours of operation. Blasting operation shall be conducted Monday through Friday only between the hours of 12:00 P.M. and 4:30 P.M. Exception: When other times are approved in writing in advance by the Fire Chief or their designated representative. RR. Amend Section 5607 Blasting of the IFC, by adding in lieu thereof a new Section 5607.4.1 Notification, which reads: Section 5607.4.1 Notification. The blaster shall have a means, approved by the fire code official, for residents within a 3-mile (15,840 feet) radius of the blast site, to elect to be notified 30 minutes in advance of any blast. The fire code official may increase notification distances at their discretion. SS. Amend Section 5607 Blasting of the IFC, by adding in lieu thereof a new Section 5607.16 Pre-blast survey, which reads: Section 5607.16 Pre-blast survey. At least 15 days before initiation of blasting, the surveyor shall notify, in writing, all residents or owners of dwellings or other structures located within 500 feet (152,400 mm) of the blasting area of the intent to conduct a preblast survey. The fire code official may identify alternate re-blast survey distances. The surveyor shall promptly conduct a pre-blast survey of the dwelling or structures and promptly prepare a written report of the survey. An updated survey of any additions, modifications, or renovations shall be performed by the surveyor if requested by the contractor or the fire code official. The surveyor shall determine the condition of the dwelling or structure and shall document any existing damage and other physical factors that could reasonably be affected by the blasting. The surveyor shall examine the interior as well as the exterior structure and shall document any damage by means of digital photographic or digital video methods. Structures such as pipelines, cables, transmission lines, cisterns, wells, and other water systems warrant special attention; however, the assessment of these structures may be limited to surface conditions and other readily available data. The written report of the survey shall be signed by the person who conducted the survey. Copies of the report shall be promptly provided to the contractor and made available to the fire code official. All surveys shall be completed by the surveyor before the initiation of blasting. All surveys shall be conducted by a disinterested third party, regularly engaged in performing pre-blast surveys. The contractor shall notify the owners of all gas, water, and petroleum pipelines in any area where blasting will be utilized. A representative of the pipeline shall be allowed to be present to observe preparations and blasting. TT. Amend Section 5607 Blasting of the IFC, by adding in lieu thereof a new Section 5607.17 Ground vibration, which reads: Section 5607.17 Ground vibration. Regardless of the distance to nearby facilities, buildings or other structures, the blasting operations shall be carried out in such a manner that they will not cause fly rock damage from air blast overpressure or ground vibration. The contractor or operator shall conduct seismic monitoring of all blasts. The seismic recording site shall be located at the nearest structure or building within 500 feet (152,400 mm) of the blast site. The maximum peak particle velocity at any such recording site shall not exceed one inch per second in any of three mutually perpendicular directions. UU. Amend Section 5607 Blasting of the IFC, by adding in lieu thereof a new Section 5607.18 Distance from structures, which reads: Section 5607.18 Distance from structures. There shall be no blasting within 100 feet (30,480 mm) of any structure or building. VV. Amend Section 5607 Blasting of the IFC, by adding in lieu thereof a new Section 5607.19 Blasting records, which reads: Section 5607.19 Blasting records. The contractor shall retain a record of all blasts for at least 3 years. Upon request, copies of these records shall be made available to the fire code official and to the public for inspection. Such records shall contain the following data: 1. Name of the contractor conducting the blast. 2. Location, date, and time of the blast. 3. Name, signature, and certificate number of blaster conducting the blast. 4. Identification, direction, and distance, in feet. From the nearest blast hole to the nearest dwelling, public building, school, church, community or institutional building outside the permit area, except those described herein. 5. Weather conditions, including those which may cause possible adverse blasting effects. 6. Type of material blasted. 7. Sketches of the blast pattern including number of holes, burden, spacing, decks, and delay pattern. 8. Diameter and depth of holes. 9. Types of explosives used. 10. Total weight of explosives detonated in an 8-millisecond period. 11. Initiation System. 12. Type and length of stemming. 13. Mats or other protections used. Seismographic and air blast records shall include: 1. Type of instrument, sensitivity, and calibration signal, or certification of annual calibration. 2. Exact location of instrument and the date, time and distance from the blast. 3. Name of the person and firm taking the reading. 4. Name of the person and firm analyzing the seismographic record. 5. The vibration and/or air blast level recorded. WW. Amend Section 5607 Blasting of the IFC, by adding in lieu thereof a new Section 5607.20 Weather, which reads: Section 5607.20 Weather. Blasting shall not be conducted when atmospheric conditions allow for temperature inversions. II. Amend by omitting Section 5704.2.9.6 Above-ground tanks outside of buildings, of the IFC, and amend by adding in lieu thereof a new Section 5704.2.9.6 Above-ground tanks outside of buildings, which reads: Section 5704.2.9.6 Above-ground tanks outside of buildings. The storage of Class I and Class II liquids in outside aboveground tanks shall be prohibited within the city limits of the City of Shawnee, Kansas except in a designated P.I. (Planned Industrial) district and then only upon approval of a site development plan, pursuant to Title 17 of the Shawnee Municipal Code, and in compliance with said Chapter insofar as the same may be relevant to the proposed stationary aboveground tank. XX. Amend by omitting Section 5706.4.5 Storage, of the IFC, and amend by adding in lieu thereof a new Section 5706.4.5 Storage, which reads: 5706.4.5 Storage. The storage of Class I, Class II, and Class III liquids in bulk plants shall be prohibited within the city limits of the City of Shawnee, Kansas except in a designated P.I. (Planned Industrial) district, and then only upon approval of a site development plan pursuant to Title 17 of the Shawnee Municipal Code, and in compliance with said Chapter insofar as the same may be relevant to the proposed bulk plant. Storage in bulk plants shall be in accordance with the International Fire Code 2012 Edition, Chapter 57.
(Ord. No. 3534, 2025)
Ask a question about Shawnee law
Corpus searches the Shawnee sections it holds and shows the ones that match, with their citations. Free, no sign-in.