25.06.134 - Standards for VE zones
The following standards apply to all areas zoned VE: A. Elevation. New construction and substantial improvement for residential structures, and for commercial, industrial, or other nonresidential structures shall be elevated on pilings and columns and have the elevation of the bottom of the lowest horizontal structural member of the lowest enclosed floor (excluding pilings or columns) at or above the flood protection elevation. B. Anchoring 1. All new construction and substantial improvements including structures attached to pilings and columns, shall be anchored to resist floatation, collapse, and lateral movement due to the effects of wind and water loads acting simultaneously on all building components. a. Water loading values used shall be those associated with the base flood. b. Wind loading values used shall be those required by applicable state or local building standards. 2. A registered professional engineer or architect shall develop or review the structural design, specifications, and plans for the construction, and shall certify that the design and methods of construction to be used are in accordance with accepted standards of practice for meeting the provisions of subsection 25.06.134.A and this subsection 25.06.134.B; and 3. For structures that are designed to float as part of their function (e.g. boat sheds, covered moorage, floating piers with structures on top), shall be securely attached to an adequately anchored foundation system that resists flotation, collapse, and lateral movement. C. Siting. New construction, not including substantial improvements, shall be located landward of the reach of mean high tide. D. Areas below the lowest floor for all new construction and substantial improvements have the space below the lowest floor either: 1. Free of obstruction; or 2. Constructed with non-supporting breakaway walls, open wood latticework, or insect screening intended to collapse under wind and water loads without causing collapse, displacement, or other structural damage to the elevated portion of the building or supporting foundation system. a. For the purposes of this subsection 25.06.134.D.2, a breakaway wall shall have a design safe loading resistance of not less than 10 and no more than 20 pounds per square foot. Use of breakaway walls which exceed a design safe loading resistance of 20 pounds per square foot (either by design or when so required by local or state codes) may be permitted only if a registered professional engineer or architect certifies that the designs proposed meet the following conditions: 1) Breakaway wall collapse shall result from a water load less than that which would occur during the base flood; and 2) The elevated portion of the building and supporting foundation system shall not be subject to collapse, displacement, or other structural damage due to the effects of wind and water loads acting simultaneously on all building components (structural and non-structural). Water loading values used shall be those associated with the base flood. Wind loading values used shall be those required by applicable state or local building standards. 3) Such enclosed space shall not be used for human habitation and shall be usable solely for parking of vehicles, building access, or storage. E. Use of fill. Fill material used for structural support of buildings is prohibited. F. Processing and storage of materials and equipment 1. Processing. As part of new construction and substantial improvements, the processing of hazardous materials and the process of using one or more operations that transforms a material into hazardous material is prohibited in special flood hazard areas. 2. Storage of materials and equipment a. Structures that store materials and equipment shall adhere to applicable flood code requirements for substantial improvement, new construction, or accessory structures. b. The storage of materials or equipment outside a structure is prohibited in special flood hazard areas unless stored in a manner that is reasonably safe from flooding. G. Utilities and attendant equipment 1. All new and replacement water supply systems shall be designed to eliminate or minimize infiltration of floodwaters into the system. 2. Water wells shall be located outside the floodway. 3. New and replacement sanitary sewage systems shall be designed to eliminate or minimize infiltration of floodwaters into the systems and discharge from the systems into floodwaters. 4. On-site waste disposal systems shall be located to avoid impairment to them or contamination from them during flooding. 5. New or replacement utilities and attendant equipment shall be: a. Located at an elevation at or above the flood protection elevation or elevated as required by ASCE 24, whichever is greater: or b. Designed and installed to prevent water from entering or accumulating within the components and to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the design flood elevation in accordance with ASCE 24; and c. Electrical wiring systems are permitted to be located below the flood protection elevation provided that they conform to the provisions of the electrical part of this code for wet locations and shall be anchored following the provisions of subsection 25.06.134.B. H. Manufactured homes. All manufactured homes to be placed or substantially improved shall be installed using methods and practices that minimize flood damage, including: 1. Having the elevation of the lowest floor at or above the flood protection elevation; 2. Having the manufactured home chassis supported by reinforced piers or other foundation elements of at least equivalent strength that are no less than the flood protection elevation in height; and 3. Meeting the anchoring requirements in subsection 25.06.134.B. I. Recreational vehicles shall: 1. Be on the site for fewer than 180 consecutive days; and 2. Be fully licensed and ready for highway use, on its wheels or jacking system, attached to the site only by quick disconnect type utilities and security devices, and have no permanently attached additions; or 3. Meet the manufactured homes requirements in subsection 25.06.134.H. J. Critical facilities 1. Construction of new critical facilities shall be located outside the limits of the special flood hazard areas and outside the limits of all other flood-prone areas as defined in Chapter 25.09 where possible. 2. Construction of new critical facilities shall be permissible within special flood hazard areas and all other flood-prone areas as defined in Chapter 25.09 if no feasible alternative site is available. 3. Critical facilities constructed within special flood hazard areas and all other flood-prone areas as defined in Chapter 25.09 shall have the elevation of the lowest floor at or above the flood protection elevation at the site or to the height of the 500-year flood if available, whichever is higher. 4. Access routes to all critical facilities shall be elevated to or above the level of the base flood elevation to the extent possible.
(Ord. 127410, § 2, 2026.)
Ask a question about Seattle law
Corpus searches the Seattle sections it holds and shows the ones that match, with their citations. Free, no sign-in.