For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 49-1547 — Master backflow preventers

Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1547

Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/f2552810-8d54-41af-b1c3-c30cb8316410

Sec. 49-1547. - Master backflow preventers.

(a) Installation of a master backflow preventer (MBFP) shall be subject to the following: (1) When required, a master backflow preventer must be installed between the meter and the first branch or fixture, appurtenance and appliance take-off. Only a reduced pressure principle backflow assembly shall be used as a master backflow preventer. (Exception: A branch isolated by a branch backflow preventer serving a lawn sprinkler system may be installed before the master backflow preventer.) (b) A master backflow preventer shall be installed at the following types of facilities: (1) Facilities with secondary or auxiliary water systems. (2) Hospitals, clinics, nursing homes or other medical buildings. (3) Any commercial or industrial facilities the chief plumbing inspector (or the water purveyor) determines to be a potential cross-connection hazard. (4) Sewage treatment plants or pumping stations. When a water heating device is installed downstream of a backflow prevention device refer to section 49-1609.

(Ord. No. 40524, § 1, 10-20-15)

Ask a question about Omaha law

Corpus searches the Omaha sections it holds and shows the ones that match, with their citations. Free, no sign-in.