§ 49-1547 — Master backflow preventers
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-1547
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/f2552810-8d54-41af-b1c3-c30cb8316410
Sec. 49-1547. - Master backflow preventers.
(a) Installation of a master backflow preventer (MBFP) shall be subject to the following: (1) When required, a master backflow preventer must be installed between the meter and the first branch or fixture, appurtenance and appliance take-off. Only a reduced pressure principle backflow assembly shall be used as a master backflow preventer. (Exception: A branch isolated by a branch backflow preventer serving a lawn sprinkler system may be installed before the master backflow preventer.) (b) A master backflow preventer shall be installed at the following types of facilities: (1) Facilities with secondary or auxiliary water systems. (2) Hospitals, clinics, nursing homes or other medical buildings. (3) Any commercial or industrial facilities the chief plumbing inspector (or the water purveyor) determines to be a potential cross-connection hazard. (4) Sewage treatment plants or pumping stations. When a water heating device is installed downstream of a backflow prevention device refer to section 49-1609.
(Ord. No. 40524, § 1, 10-20-15)