28-21. - Construction requirements for existing buildings.
Section 1103.8 of the code is hereby amended by adding a new Section 1103.8.2.1 entitled "Interconnection for R-3 and R-4 group homes" to read as follows: 1103.8.2.1 Interconnection for R-3 and R-4 group homes. All smoke detectors located in R-3 and R-4 group occupancy types shall be interconnected in such a manner that the activations of one alarm will activate all of the alarms in the individual unit. Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of one alarm. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. The exceptions in Section 1103.8.2 do not apply.
(Ord. No. 5111, § 3(Exh.), 12-9-24, eff. 7-1-25)