Sec. 42-90. - Insulation of guy wires.

(a) Guy wires on poles supporting any wire or wires shall be insulated and maintained as set forth in this section. (b) An insulator shall be located in each guy which is attached to a pole or structure carrying any supply conductors of more than one hundred (100) volts to ground and not more than fifteen thousand (15,000) volts, or in any guy which is exposed to such voltages. This guy insulator shall be located at least eight (8) feet above the ground. (c) Where a guy attached to any pole carrying communication or supply conductors or both is carried over or under any overhead supply conductor of more than one hundred (100) volts to ground, and where a hazard would otherwise exist, two (2) or more guy insulators shall be placed so as to include the exposed section of the guy between them as far as possible. Neither insulator shall be within eight (8) feet of the ground. (d) Guy insulators shall be made of wet process porcelain, wood or other material of suitable mechanical and electrical properties. Such insulators shall have a dry flash-over voltage at least double the normal line voltage and a wet flash-over voltage at least as high as the normal line voltage between conductors. (e) Guy insulators shall have a mechanical strength at least equal to that required of the guys in which they are installed. (f) Where guys in which it is necessary to install insulators are so arranged that one crosses or is above another, insulators shall be so placed that, in case any guy sags down upon another, the insulators will not become ineffective. (g) A guy insulator or insulators are not required, if the guy is attached to a pole on a private right-of-way, which pole carries no supply circuits whose voltage exceeds two hundred fifty (250) volts or whose transmitted power exceeds three thousand two hundred (3,200) watts. (h) A guy insulator is not required, if all supply conductors are cabled having effectively grounded continuous metal sheath or insulated conductors supported on and cabled together with an effectively grounded messenger. (i) Insulators are not required in guys under any one of the following conditions: (1) Where the guy is electrically connected to grounded steel structures or to an effective ground connection on wood poles. (2) Where the guys are uniformly effectively grounded throughout any system of overhead lines. (3) Where the guys are connected to a line conductor which has at least four (4) ground connections in each mile of line, in addition to the ground connections at individual services.

(Code 1958, § 35-10.1)

Ask a question about Norfolk law

Corpus searches the Norfolk sections it holds and shows the ones that match, with their citations. Free, no sign-in.