Burlington Code of Ordinances § 13-63 Generally.
13-63 Generally.
(a) Except as otherwise provided, no person or organization shall maintain, own, erect or construct any building or structure which is used for commercial, multifamily, or institutional use or any part thereof or cause the same to be done which fails to support adequate radio coverage to the fire department.
(b) For purposes of this section, adequate radio coverage shall include all of the following: A. A minimum signal strength of -101 dBm available in ninety-five (95) percent of the area of each floor of the building when transmitted from the public safety radio communications system; and B. A minimum signal strength of -101 dBm received at the public safety radio communications system when transmitted from ninety-five (95) percent of the area of each floor of the building, via portable radio with public safety microphone.
(c) Channel performance criterion (CPC). CPC is the minimum performance level in a faded channel, per TSB-88, clause 4.2. TSB-88 is a "Telecommunications Systems Bulletin" published by the TIA, Telecommunications Industry Association. The performance level is rated using "Delivered Audio Quality." Industry standard DAQ definitions are shown in Table 1. 2. DAQ level of 3 is the minimum performance level which shall be attainable by public safety radio systems in ninety-five (95) percent of the area of each floor of a building subject to this chapter.
Table 1. Delivered Audio Quality Definitions
DAQ Delivered Audio Quality | Subjective Performance Description
1 | Unusable, speech present but unreadable.
2 | Understandable with considerable effort. Frequent repetition due to noise/distortion.
3 | Speech understandable with slight effort. Occasional repetition required due to noise/distortion.
3.5 | Speech understandable with repetition only rarely required. Some noise/distortion.
4 | Speech easily understood. Occasional noise/distortion.
4.5 | Speech easily understood. Infrequent noise/distortion
5 | Speech clearly understood.
(d) The frequency range which must be supported shall be 460.62 MHz from the trunked system communications base stations, and the public safety radio communications base stations.
(e) The fire department may alter necessary frequencies or signal strengths due to changes in technical specification for public safety radio requirements. In such event, any frequency changes shall be reported to the city council and approved as amendments to this chapter as soon as is practicable.
(Ord. of 10-26-09(1))