Annual tests.
Biloxi Code of Ordinances § 5-17-11
in effectSec. 5-17-11. - Annual tests.
(a) Once an in-building radio amplifier system is installed, the building owner shall test all active components of the system including but not limited to amplifier, power supplies, and back-up batteries, a minimum of once every 12 months.
(b) Amplifiers shall be tested to ensure that the gain is the same as it was upon initial installation and acceptance.
(c) Back-up batteries and power supplies shall be tested under load for a period of one hour to verify that they will operate during an actual power outage.
(d) All other radio signal radiating components shall be checked to determine that they are operating within the manufacturer's specifications for the intended purpose.
(Ord. No. 2026, § 2, 3-7-06)