Sec. 49-1112. - Automatic grease removal device sizing.
To determine the maximum possible flow of the inlet pipe, refer to Table 49-1112 below:
Table 49-1112
Load | Demand | Load | Demand | Load | Demand
(F U) | (G P M) | (F U) | (G P M) | (F U) | (G P M)
1 | 3.0 | 17 | 18.4 | 140 | 52.5
2 | 5.0 | 18 | 18.8 | 160 | 57.0
3 | 6.5 | 19 | 19.2 | 180 | 61.0
4 | 8.0 | 20 | 19.6 | 200 | 65.0
5 | 9.4 | 25 | 21.5 | 225 | 70.0
6 | 10.7 | 30 | 23.3 | 250 | 75.0
7 | 11.8 | 35 | 24.9 | 275 | 80.0
8 | 12.8 | 40 | 26.3 | 300 | 85.0
9 | 13.7 | 45 | 27.7 | 400 | 105.0
10 | 14.6 | 50 | 29.1 | 500 | 124.0
11 | 15.4 | 60 | 32.0 | 750 | 170.0
12 | 16.0 | 70 | 35.0 | 1,000 | 208.0
13 | 16.5 | 80 | 38.0 | 1,250 | 238.0
14 | 17.0 | 90 | 41.0 | 1,500 | 269.0
15 | 17.5 | 110 | 43.5 | 1,750 | 297.0
16 | 18.0 | 120 | 48.0 | 2,000 | 325.0
To determine the fixture units connected to the pipe, refer to the table in section 49-901.
_____
(Ord. No. 40524, § 1, 10-20-15)