§ 34.508 — FIRE COMMAND CENTER

Madison General Ordinances (Rev. 28, Update 3: codified through ORD-26-00040, published August 3, 2026) · Madison General Ordinances § 34.508

Corpus is an independent public-information project, not the official City of Madison website. Stable reference: corpuslaw.us/code/f5ab77f3-8bd5-4add-a860-8d909a292215

34.508 - FIRE COMMAND CENTER.

(1) The following requirements are in addition to the requirements found in IFC section 508.1.1: (a) The fire command center door shall be visible from the building main entrance unless otherwise approved by the Fire Chief. (2) The following requirements are in addition to the requirements found in IFC section 508.1.6, item 5: (a) The status indicators and controls for air-handling systems required in subsection 5., shall be provided on the fire-fighters control panel, with the appearance and performance required in IFC section 909.16.

(Am. by ORD-11-00004, 1-12-11; ORD-13-00102, 6-12-13; Rpld. & Recr. by ORD-22-00122, 12-3-22)