Sec. 7-188. - Backflow prevention assembly requirement.

(a) Elimination and protection of cross connections. Cross connections occurring within the water system shall be eliminated or protected with the appropriate backflow preventer. Cross connections are eliminated by establishing an air gap between the potable and non-potable sources. Cross connections are protected by installing the appropriate backflow preventer. It shall be the responsibility of the owner of the cross connection to eliminate the cross connection or protect the cross connection with a backflow preventer approved by the water system. (b) Connections to sewer. Direct connections, permanent or temporary, between the water system and a sanitary or storm sewer are prohibited. (c) Home wells. Connections to any source of water other than that provided by the water system including home wells, is prohibited unless a backflow preventer approved by the water system is installed. (d) Approved backflow prevention assemblies. Only backflow prevention assemblies approved by the state department of health shall be installed on the city's water system to comply with this division. (e) Installation requirements. Reduced pressure principle assemblies, double check valve assemblies, and pressure vacuum breakers shall be installed in a manner and location that provides adequate access for testing and repair of the assembly. Reduced pressure principle assemblies and double check valve assemblies shall not be subject to possible flooding. Reduced pressure principle assemblies and double check valve assemblies shall not be installed in a pit or enclosure below ground level.

(Ord. No. 00-0003, § 3, 4-4-00; Ord. No. 19-004, 3-14-19)

Ask a question about Greenville law

Corpus searches the Greenville sections it holds and shows the ones that match, with their citations. Free, no sign-in.