For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18.79.070 — Methane gas mitigation design requirements

Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.79.070

Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/fab87b99-a475-41e0-bfe0-cf70d9154e1f

18.79.070 - Methane gas mitigation design requirements.

The development project shall provide a methane gas mitigation system with the required mitigation features indicated in Table 1 of this section. TABLE 1 METHANE GAS MITIGATION SYSTEM DESIGN REQUIREMENTS SITE DESIGN LEVEL b MITIGATION FEATURE REQUIREMENTS a | LEVEL I | LEVEL II | LEVEL III Methane Gas Membrane Barrier | X | X | X Perforated Subslab Vent Piping | X | X | X Vertical Vent Risers | X | X | X Methane Gas Detection System (in-room and vent risers) | X | X Methane Gas Alarm System | X | X Control Panel | X | X Mechanical Ventilation | X | X Mechanical Subslab Extraction | X Pavement Venting | X | X Signs | X | X | X Conduit or Cable Seal Fittings | X | X | X Trench Dam | X | X | X

(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022)

Ask a question about Long Beach law

Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.