18.79.070 - Methane gas mitigation design requirements.
The development project shall provide a methane gas mitigation system with the required mitigation features indicated in Table 1 of this section. TABLE 1 METHANE GAS MITIGATION SYSTEM DESIGN REQUIREMENTS SITE DESIGN LEVEL b MITIGATION FEATURE REQUIREMENTS a | LEVEL I | LEVEL II | LEVEL III Methane Gas Membrane Barrier | X | X | X Perforated Subslab Vent Piping | X | X | X Vertical Vent Risers | X | X | X Methane Gas Detection System (in-room and vent risers) | X | X Methane Gas Alarm System | X | X Control Panel | X | X Mechanical Ventilation | X | X Mechanical Subslab Extraction | X Pavement Venting | X | X Signs | X | X | X Conduit or Cable Seal Fittings | X | X | X Trench Dam | X | X | X
(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022)