§ 173.11.08 — Fuel-gas equipment and installations in mobile home parks

Code of Ordinances, City of Springfield, Illinois (Supp. No. 82: codified through Ordinance No. 146-04-26, enacted April 7, 2026) · Springfield, Ill., City Code § 173.11.08

Corpus is an independent public-information project, not the official City of Springfield website. Stable reference: corpuslaw.us/code/fb76c079-5d95-4c10-8f27-189678c73bf9

§ 173.11.08. - Fuel-gas equipment and installations in mobile home parks.

(a) General. Except as otherwise permitted or required by this section, fuel-gas equipment and installations in mobile home parks shall comply with the provisions of this section. The provision of this section do not apply to the mobile home gas piping and equipment installed as part of the home. (b) Required gas supply. The minimum hourly volume of gas required at each mobile home lot outlet or any section of the mobile home park gas piping system shall be calculated as shown in the table in this section. (c) Installation. Gas piping installed below ground shall have a minimum earth cover of 12 inches. (d) Location. Gas piping shall not be installed underground beneath buildings or that portion of the mobile home lots reserved for the location of mobile homes, mobile home accessory buildings or structures, concrete slabs or automobile parking, unless installed in a gas-tight conduit. The conduit shall be approved for installation underground beneath buildings and not less than Schedule 40 pipe. The interior diameter of the conduit shall be not less than ½ inch larger than the outside diameter of the gas piping. The conduit shall extend to a point not less than 12 inches beyond any area where it is required to be installed or the outside wall of a building and the outer ends shall not be sealed. Where the conduit terminates within a building, it shall be readily accessible and the space between the conduit and the gas piping shall be sealed to prevent leakage of gas into the building. A gas piping lateral terminating in a mobile home lot outlet riser surrounded by a concrete slab shall not be required to be installed in a conduit provided the concrete slab is entirely outside the wall line of the mobile home, is not continuous with any other concrete slab and is used for stabilizing other utility connections. (e) System shutoff valve. A readily accessible and identified shutoff valve controlling the flow of gas to the entire gas piping system shall be installed near the point of connection to the service piping or supply connection of the liquefied petroleum gas tank. (f) Mobile home lot shutoff valve. Each mobile home lot shall have an approved gas shutoff valve and union installed upstream of the mobile home lot gas outlet and located on the outlet riser at a height not less than 12 inches above grade. Valve and union shall not be located under a mobile home. When the mobile home lot outlet is not in use, the outlet shall be equipped with an approved cap or plug to prevent accidental discharge of gas. (g) Mobile home lot gas outlet. Each mobile home lot piped for gas shall be provided with an individual outlet riser at the mobile home lot. The mobile home lot gas outlet shall terminate with the service connection located within a four-foot area in the rear third section of the mobile home lot on the left (road) side of the mobile home, with respect to the location, or proposed location, of the mobile home on the lot. (h) Mobile home connector. Each mobile home shall be connected to the mobile home lot outlet by an approved mobile home connector, a maximum of six feet in length or schedule 40 black iron pipe. Approved pipe and fittings may be used between the flexible connector and the mobile home lot gas outlet when the distance between the mobile home lot gas outlet and the mobile home gas service connection exceeds that required to make a safe installation with only a mobile home connector. Gas connectors shall be of a size to adequately supply the total demand of the connected mobile home. (i) Mechanical protection. Gas outlet risers, regulators, meters, valves or other exposed equipment shall be protected from mechanical damage by vehicles or other causes. Such protection may consist of posts, fencing or other permanent barriers. Atmospherically controlled regulators shall be installed in such a manner that moisture cannot enter the regulator vent and accumulate above the diaphragm. Where the regulator vent may be obstructed due to snow and icing conditions, shields, hoods, or other suitable devices shall be provided to guard against closing the vent opening. (j) Gas meters. Meters shall not be installed in unventilated or inaccessible locations, nor closer than three feet to sources of ignition. When meters are installed, they shall not depend on the gas outlet riser for support, but shall be adequately supported by a post or bracket placed on a firm footing, or other means of providing equivalent support. (k) Gas piping size. The size of each section of natural gas or LP-gas piping systems shall be determined as specified in this chapter. (l) Maintenance. The operator of the mobile home park shall be responsible for maintaining gas piping installations and equipment in good working condition. Minimum Demand Factors For Calculating Gas Piping Systems in Mobile Home Parks Number of Mobile Home Sites | Demand Factor Btu/h Mobile Home Site 1 | 125,000 2 | 117,000 3 | 104,000 4 | 96,000 5 | 92,000 6 | 87,000 7 | 83,000 8 | 81,000 9 | 79,000 10 | 77,000 11 to 20 | 66,000 21 to 30 | 62,000 31 to 40 | 58,000 41 to 60 | 55,000 Over 60 | 50,000

(Ord. No. 826-12-06, § 1(Exh. A), 12-19-06)

Ask a question about Springfield law

Corpus searches the Springfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.