§ 385.23 — Prohibited Uses and Methods of Storage
Codified Ordinances of the City of Cleveland, Ohio (2026 S-28: current through legislation passed October 19, 2026) · Codified Ordinances of Cleveland § 385.23
Corpus is an independent public-information project, not the official City of Cleveland website. Stable reference: corpuslaw.us/code/fbcf8446-bb25-454d-ab97-2f9de6a45c26
§ 385.23 Prohibited Uses and Methods of Storage
(a) Calcium carbide and acetylene generated therefrom shall not be used for interior lighting, room or space heating or cooking. (b) No person shall generate, transport, store or sell acetylene compressed to a pressure greater than fifteen (15) pounds to the square inch except when it is dissolved in acetone or other suitable medium and confined in a cylinder conforming to the specifications of the Interstate Commerce Commission. All such cylinders shall be, or shall have been, tested at the time of manufacture, and no cylinders shall be used which do not meet such test requirements. (c) No person shall compress and dissolve acetylene so that the solution pressure exceeds two hundred fifty (250) psi at seventy degrees Fahrenheit (70°F), or transport, store or sell dissolved acetylene when the solution pressure exceeds such pressure at seventy degrees Fahrenheit (70°F). (d) No person shall transfer any portion of the contents of one (1) acetylene cylinder into another acetylene cylinder or mix any other gas with acetylene in an acetylene cylinder. (Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
Ask a question about Cleveland law
Corpus searches the Cleveland sections it holds and shows the ones that match, with their citations. Free, no sign-in.