17.12.630 - Amendment of Section 903 of the 2025 California Fire Code.
A. Subsection 903.2 of the 2025 California Fire Code is amended to read as follows: 903.2 Where required. Approved automatic sprinkler systems shall be provided in the locations described in the following: 1. Throughout existing buildings and structures where an increase is made to the floor area that results in the building exceeding 10,000 square feet or the proposed change in use or contents of the building creates a higher risk, as indicated in Section 102.3 of the California Fire Code. 2. Throughout existing one- and two-family dwellings where an increase of over 500 square feet is made to the floor area that results in the building exceeding 3,600 square feet. 3. Throughout buildings and structures that are four or more stories in height, regardless of the floor area. 4. Throughout new buildings and structures that exceed 6,200 square feet. 5. Throughout new buildings and structures described in Section 903.2.1 through 903.2.20 as modified herein. B. Subsection 903.2.2.1 of the 2025 California Fire Code is amended to read as follows: 903.2.2.1 Ambulatory care facilities. An automatic sprinkler system shall be installed throughout the entire floor containing an ambulatory care facility where either of the following conditions exist at any time: 1. Four or more care recipients are incapable of self-preservation. 2. One or more care recipients that are incapable of self-preservation are located at other than the level of exit discharge serving such a facility. In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor as well as the floors below where such care is provided, and all floors between the level of ambulatory care and the nearest level of exit discharge, and all floors below the level of exit discharge. Exception: Deleted C. Subsection 903.2.8 of the 2025 California Fire Code is amended to read as follows: 903.2.8.4 Balconies and decks. Sprinkler protection shall be provided for exterior balconies, decks and ground floor patios of dwelling units and sleeping units, provided there is a roof or deck above. Sidewall sprinklers that are used to protect such areas shall be permitted to be located such that their deflectors are within 1 inch (25 mm) to 6 inches (152 mm) below the structural members and a maximum distance of 14 inches (356 mm) below the deck of the exterior balconies and decks that are constructed of open wood joist construction. Balconies and decks located more than 2 stories above other balconies or decks, shall not be required to have sprinkler protection. D. Subsection 903.2.18 of the 2025 California Fire Code is amended to read as follows: 903.2.18 Group U private garages and carports accessory to R-3 occupancies. Carports with habitable space above and attached garages, accessory to Group R-3 occupancies, shall be protected by residential fire sprinklers in accordance with this section. Residential fire sprinklers shall be connected to and installed in accordance with an automatic residential fire sprinkler system that complies with Section R313 of the California Residential Code or with NFPA 13D. Fire sprinklers shall be residential sprinklers or quick-response sprinklers, designed to provide a minimum density of 0.05 gpm/ft2 (2.04 mm/min.) over the area to the garage and/or carport, but not to exceed two sprinklers for hydraulic calculation purposes. Garage doors shall not be considered obstructions with respect to sprinkler placement. Exception: Deleted. E. Subsection 903.3.1.2.1 of the 2025 California Fire Code is amended to read as follows: 903.3.1.2.1 Balconies and decks. Refer to Section 903.2.8.4 amendment. F. Section 903.3.1.2.3 of the 2025 California Fire Code is amended to read as follows: 5. Attic Protection. Where sprinkler protection is not required by CFC 903.3.1.2.3.1 through 903.3.1.2.3.4, then pilot sprinklers shall be provided in the attics and between floors where floor/ceiling assemblies consist of open web wood joists or trusses. Pilot sprinklers shall be intermediate temperature-rated, K = 4.2, with quick response. Pilot sprinklers shall be located within 12 inches (30.48 cm) of the structure and/or at the apex of each ridgeline when applicable. A sprinkler is required where the ridgeline and hips converge. Sprinklers shall be spaced at maximum of 30 feet (9.144 m) centers (maximum 15 feet (4.572 m) from outside walls) and shall be located at all heat and fire sources, including furnaces, hot water heaters, above kitchen ranges, etc. G. Subsection 903.4.1 of the 2025 California Fire Code Section 903 is amended to read as follows: 903.4.1 Electronic supervision. Valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, waterflow switches on all sprinkler systems, and commercial kitchen hood & duct fixed extinguishing systems shall be electrically supervised by a listed fire alarm control unit. Exceptions: 1. Automatic sprinkler systems protecting one- and two-family dwellings. 2. Limited area sprinkler systems in accordance with Section 903.3.8, provided that backflow prevention device test valves located in limited area sprinkler system supply piping shall be locked in the open position unless supplying an occupancy required to be equipped with a fire alarm system, in which case the backflow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated. 3. Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided. 4. Jockey pumps control valves that are sealed or locked in the open position. 5. Control valves to paint spray booths or dip tanks that are sealed or locked in the open position. 6. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position. 7. Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position. 8. Underground key or hub gate valves in roadway boxes. 9. Commercial kitchen hood & duct fixed extinguishing systems located in buildings where a sprinkler monitoring system is or was not required.
(Ord. 31258.)
Ask a question about San Jose law
Corpus searches the San Jose sections it holds and shows the ones that match, with their citations. Free, no sign-in.