§ 94.40. - Fire hydrant requirements.

(a) An approved water supply capable of supplying required fire flow for fire protection shall be provided to all premises in the jurisdiction upon which buildings or portions of buildings are constructed after April 26, 1996. Except for R-3 occupancies as defined in the 2018 International Fire Code, when any portion of the building protected is in excess of 250 feet from a water supply on a public street, there shall be provided, when required by the fire code official, on-site fire hydrants and mains capable of supplying the required fire flow as determined in Appendix B of the 2018 International Fire Code. (b) The type of fire hydrant, including number, size, and arrangement of outlets, the size of the main valve opening and the size of barrel shall be approved by the office of public utilities based upon the required fire flow; provided, however, the fire hydrants shall not have less than a six-inch connection with the mains, and a gate valve shall be installed in the fire hydrant connection. (c) There shall be an approved fire hydrant as described in subsection (b) above to all R-3 occupancies. Said hydrant shall be placed within 600 feet of any portion of the building protected. (d) There shall be an approved fire hydrant within 150 feet of travel distance of the department connection servicing sprinkler or standpipe systems. Beginning January 1, 2023, any newly constructed building shall have a fire hydrant located 100 feet of travel distance of the fire department connection "FDC" servicing a fire system standpipe system as required by section 507 of the International Fire Code. (e) No object shall be constructed, maintained, or installed within 48 inches of a fire hydrant. It shall be unlawful to install, maintain, construct, or enlarge any barriers, trees, bushes, walls, or other obstacles, which may hide or impede the use of the fire hydrant. (f) There shall be vehicle protection measures equivalent to the following specifications when it is determined that a fire hydrant requires protection from possible vehicular damage due to proximity to alleys, driveways, or parking areas: This is covered in 2018 IFC section 312. (1) Posts shall be a minimum of four-inch steel pipe filled with concrete or be of a material with equivalent strength. (2) Posts shall be a minimum of 36 inches in height above ground level. (3) Posts shall extend a minimum of 36 inches below grade and be set in concrete. (4) Posts shall be a minimum of 48 inches away from the hydrant. (5) Posts shall be set on all sides of the hydrant, which may subject to the vehicular damage. (6) Post shall be spaced not more than four feet between posts on center. (g) Any equivalent measures used for vehicular protection shall first be approved by the fire safety division before implementation.

(Ord. No. 190-04-06, § 1(Exh. A), 4-4-06; Ord. No. 489-07-07, § 1(Exh. A), 7-17-07; Ord. No. 056-02-23, § 1(Exh. A), 2-21-23)

Ask a question about Springfield law

Corpus searches the Springfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.