§ 5704-02 — Precision Testing of Certain Underground Storage Systems

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · 3 RCNY § 5704-02

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/fdd13831-34c5-4d7d-861c-58446064206c

§ 5704-02 Precision Testing of Certain Underground Storage Systems.

(a) Scope. This section sets forth standards, requirements and procedures for precision testing pursuant to FC 5704.2.11.6 of underground storage systems for motor fuels or other flammable and combustible liquids when such systems utilize single-walled tanks, or other tanks not provided with a leak detection system meeting Fire Code requirements. (b) General Provisions. (1) Applicability. Precision testing of underground storage systems for motor fuels or other flammable and combustible liquids that utilize single-walled tanks, or other tanks not provided with a leak detection system meeting Fire Code requirements, shall be conducted in compliance with the requirements of FC Chapters 23 and 57 and this section. (2) Precision testing standard. Precision testing of underground storage systems shall be conducted in accordance with National Fire Protection Association (NFPA) Standard 329 (2005 edition). (3) Supervision. (A) Certificate requirements. Precision testing of underground storage systems shall be conducted by a person holding a certificate of license or under the general supervision of a certificate of license holder. Such person shall be trained and knowledgeable in the use of the precision test equipment and procedures for the conduct of the particular precision test. Any person conducting such test under the supervision of a certificate of license holder shall hold a certificate of fitness for such precision test. A separate certificate of fitness shall be obtained for each type of precision test system. (B) Presence on premises. The certificate holder conducting the precision test shall remain on the premises while such test is being conducted and until the system has been returned to good working order in accordance with 3 RCNY § 5704-02(c)(1)(C). (c) Operational Requirements. (1) Administrative requirements. (A) Notification of tests. Prior to conducting a precision test of a underground storage system, notification shall be made to the Bureau of Fire Prevention by calling the telephone number designated by the Bulk Fuel Unit. Tests may be witnessed by a Department representative. Tanks located within buildings shall not be tested unless prior Department approval is received. (B) Submission of test results. A report of the results of the precision test shall be submitted to the Bulk Fuel Unit of the Bureau of Fire Prevention on an approved form no later than 30 days after conducting the test. Such test report shall include the name and certificate of fitness number of the person who conducted the test, as well as the name and signature of the certificate of license holder under whose supervision the test was conducted. (C) Notification of defective storage systems. Underground storage systems shall be returned to service in good working order upon completion of the precision testing. Storage systems determined to be defective shall be removed from service in accordance with applicable laws, rules and regulations. If hazardous material has been released to the environment, notification shall be immediately made to the Department and the New York State Department of Environmental Conservation. (2) Testing equipment requirements. (A) Only approved precision testing systems shall be used for precision testing of underground storage systems. Such testing systems, including hoses and other devices and components, shall be designed for twice the maximum operating pressures of the pressures generated by the precision test system, and shall be compatible with the hazardous material stored in the tank to be precision tested. (B) All testing equipment to be placed in the storage tank, or used in the vicinity of the test area, shall be intrinsically safe or suitable for use in hazardous locations. (C) Interlocks shall be provided for all electrical connections to ensure that the system is grounded before power can be supplied. (3) Testing procedures. (A) The test area shall be cordoned off by portable barricades, signs, rope or tape to prevent unauthorized persons and motor vehicles from entering the area. Signs posted at the barricade perimeter shall be provided to read "NO SMOKING-NO OPEN FLAMES". (B) All sources of ignition, including all motor vehicles, shall be removed from the testing area. (C) Approved procedures shall be used in filling tanks and piping for precision testing, to ensure safety and prevent overfilling. Filling of tanks shall only be conducted through approved fill boxes from approved cargo tanks and/or approved safety cans. For purposes of topping off the tank or the test equipment, flammable and combustible liquids shall be drawn from an approved storage system on the premises into an approved safety can not exceeding a capacity of two and one half (2 1/2) gallons. Flammable and combustible liquids may not be withdrawn from the fuel tanks of motor vehicles. (D) To avoid erroneous results, each precision test shall compensate for temperature changes, tank-end deflection, air pockets, water tables and other variables, as set forth in NFPA 329, to avoid erroneous results. (E) Tests shall be conducted for the period of time recommended by the manufacturer of the particular precision testing system, or until accurate results can be obtained. (F) If test wells must be drilled on the site to locate the water table, the certificate of license holder shall take all necessary steps to ensure that such test wells do not disturb utility infrastructure. (G) When underground storage systems storing liquid of varying or unknown coefficients of thermal expansion are to be tested, the liquid shall be removed, the tank cleaned, and the test conducted using a material of similar viscosity and a known coefficient of expansion. (H) Power to electrical equipment shall not be turned on until all electrical connections have been made. The connection to the power source shall be the final connection made. (I) Precision testing systems shall be arranged such that rain water cannot enter the tank through the tank openings. (d) Portable Fire Extinguisher Requirements. (1) A portable fire extinguisher having at least a 40-B:C rating shall be readily accessible during testing. The maximum travel distance to the fire extinguisher shall be 30 feet and the portable fire extinguisher shall be positioned at a safe location within the testing area. (Renumbered and amended City Record 9/20/2023, eff. 10/20/2023)

Ask a question about New York law

Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.