Sec. 10-502. Fire Hydrants
Fire hydrants and valves are required for all subdivisions and additions and must be located to satisfy the requirements of the fire department. Fire hydrants shall be located in accordance with the Design Guidelines for Subdivision Improvements and 30 T.A.C. 290, Subchapter D, “Rules and Regulations for Public Water Systems,” or successor and must be approved by the applicable fire protection unit. To eliminate future street openings, all underground utilities for fire hydrants, together with the fire hydrants themselves and all other supply improvements, must be installed before any final paving of a street shown on the subdivision plat. Reflective fire hydrant buttons must be installed in all streets at a point adjacent to fire hydrants. The buttons must conform to Water Utilities and Fire Department specifications. At corner locations, buttons must be installed in both streets.