§ 25-208 — Pretreatment of wastewater
Municipal Code of the City of Fort Smith, Arkansas (Codified through Ordinance No. 126-24, enacted December 3, 2024. (Supp. No. 4)) · Fort Smith Municipal Code § 25-208
Corpus is an independent public-information project, not the official City of Fort Smith website. Stable reference: corpuslaw.us/code/ad42fa5c-e720-4612-8339-4d7c38fae1a2
Sec. 25-208. - Pretreatment of wastewater.
(a) Pretreatment facilities. Users shall provide wastewater treatment as necessary to comply with this division and shall achieve compliance with all categorical pretreatment standards, local limits, and the prohibitions set out in section 25-207(a) within the time limitations specified by EPA, the state, or the control authority, whichever is more stringent. Any facilities necessary for compliance shall be provided, operated, and maintained at the user's expense. Detailed plans describing such facilities and operating procedures shall be submitted to the control authority for review, and shall be acceptable to the control authority before such facilities are constructed. The review of such plans and operating procedures shall in no way relieve the user from the responsibility of modifying such facilities as necessary to produce a discharge acceptable to the control authority under the provisions of this division. (b) Additional pretreatment measures. (1) Whenever deemed necessary, the control authority may require users to restrict their discharge during peak flow periods, designate that certain wastewater be discharged only into specific sewers, relocate and/or consolidate points of discharge, separate sewage wastestreams from industrial wastestreams, and such other conditions as may be necessary to protect the POTW and determine the user's compliance with the requirements of this division. (2) The control authority may require any person discharging into the POTW to install and maintain, on his property and at his expense, a suitable storage and flow-control facility to ensure equalization of flow. An individual wastewater discharge permit or a general permit may be issued solely for flow equalization. (3) Grease, oil, and sand interceptors shall be provided when, in the opinion of the control authority, they are necessary for the proper handling of wastewater containing excessive amounts of grease and oil, or sand; except that such interceptors shall not be required for residential users. All interception units shall be of a type and capacity approved by the control authority, shall be so located to be easily accessible for cleaning and inspection. Such interceptors shall be inspected, cleaned, and repaired by the user at his expense. (4) FOG control devices. Facilities generating fats, oils, or greases as a result of food manufacturing, processing, preparation, or food service are not subject to the pretreatment requirements of this division; however such facilities shall comply with all applicable requirements for FOG control devices. (5) Sampling and measurement manhole. When required by the control authority, the owner of any property serviced by a building sewer carrying industrial wastes shall install a suitable control manhole together with such necessary appurtenances in the building sewer to facilitate observation, sampling and measurement of the wastes. Such manhole, when required, shall be accessible and safely located and shall be constructed in accordance with plans approved by the control authority. The manhole shall be installed by the owner at the owner's expense and shall be maintained by the owner so as to be safe and accessible at all times. (6) Users with the potential to discharge flammable substances may be required to install and maintain an approved combustible gas detection meter. (7) Upon a finding by the control authority of the necessity for proper operation of the wastewater facility of an IU, the IU shall have a licensed wastewater treatment operator on duty at all times when treating and discharging regulated wastewater to the POTW. Said operator shall meet the license or level of operator qualifications deemed necessary for proper treatment per the state pollution control and ecology commission's regulation #3. (c) Accidental discharge/slug discharge control plans. The control authority shall evaluate whether each SIU needs an accidental discharge/slug discharge control plan or other action to control slug discharges. The control authority may require any user to develop, submit for approval, and implement such a plan or take such other action that may be necessary to control slug discharges. Alternatively, the control authority may develop such a plan for any user. An accidental discharge/slug discharge control plan shall address, at a minimum, the following: (1) Description of discharge practices, including nonroutine batch discharges; (2) Description of stored chemicals; (3) Procedures for immediately notifying the control authority of any accidental or slug discharge, as required by section 25-212(f); and (4) Procedures to prevent adverse impact from any accidental or slug discharge. Such procedures include, but are not limited to, inspection and maintenance of storage areas, handling and transfer of materials, loading and unloading operations, control of plant site runoff, worker training, building of containment structures or equipment, measures for containing toxic organic pollutants, including solvents, and/or measures and equipment for emergency response. (d) Hauled wastewater. Hazardous waste will not be accepted by truck or liquid waste hauler at the POTW. (1) Septic tank waste may be introduced into the POTW only at locations designated by the control authority, and at such times as are established by the control authority. Such waste shall not violate section 25-207 of this division or any other requirements established by the control authority. The control authority shall require septic tank waste haulers to obtain individual septic tank truck discharge permits. (2) The control authority may require haulers of industrial waste to obtain individual wastewater discharge permits. The control authority may require generators of hauled industrial waste to obtain individual wastewater discharge permits. The control authority also may prohibit the disposal of hauled industrial waste which are known or reasonably suspected to contain pollutants which could result in pass through or interference. The discharge of hauled industrial waste is subject to all other requirements of this division. If the industrial waste is from a categorical user, the hauled wastewater must include analytical reports proving it meets the required limitations of its respective category. (3) Domestic waste haulers and industrial waste haulers may discharge loads only at locations designated by the control authority. No load may be discharged without prior consent of the control authority. The control authority may collect samples of each hauled load to ensure compliance with applicable standards. The control authority may require the industrial waste hauler to provide a waste analysis of any load prior to discharge. (4) Domestic waste haulers and industrial waste haulers must provide a to the control authority waste-tracking form for every load. This form shall include, at a minimum, the name and address of the industrial waste hauler, permit number, truck identification, names and addresses of sources of waste, and volume and characteristics of waste. The form shall identify the type of industry, known or suspected waste constituents, and whether any wastes are RCRA hazardous wastes. (5) Any waste not deemed domestic by the city will be handled on a case by case basis at the discretion of the control authority.
(Code 1992, § 25-208; Ord. No. 27-16, § 1(att.), 4-19-2016)
Ask a question about Fort Smith law
Corpus searches the Fort Smith sections it holds and shows the ones that match, with their citations. Free, no sign-in.