Sec. 22-94. - Additional rules and regulations.
(a) There shall be a main disconnect within five feet of any electric meter installed within the city except in extreme or unusual circumstances it may be located a greater distance by approval of the electrical inspector. (b) Every electrical contractor engaged in electrical contracting in the city shall be required to carry liability insurance as set out below: (1) Bodily injury, each occurrence .....$300,000.00 (2) Property damage, each occurrence .....$25,000.00 (c) All underground service to a structure, light, sign, or other electrical device shall have a minimum of 24 inches of cover to the top of the conduit unless written approval is obtained from the chief building official. (d) All construction within the City of Springdale shall have two ground rods installed and bonded together with any other available means of grounding.
(Code 1973, § 10-3.1; Ord. No. 2134, § 1, 9-22-92; Ord. No. 2962, § 3, 1-11-00; Ord. No. 3183, § 1, 2-12-02; Ord. No. 3346, § 3, 7-8-03; Ord. No. 3472, § 1, 3-23-04; Ord. No. 3798, § 3, 11-22-05; Ord. No. 4029, § 1, 2-13-07)