24-162 - Cooling.

(a) Conservation Requirements. All new non-residential customers shall comply with all applicable cooling requirements set forth in the second management plan from the Arizona Department of Water Resources until the first compliance date for any substitute requirement in the third management plan. A large cooling user shall: (1) Achieve a ratio of concentration that results in blowdown water being discharged at an average annual minimum of two thousand (2,000) milligrams per liter of total dissolved solids (mg/l TDS); (2) Use non-groundwater make-up water sources where available and of suitable quality; (3) Develop and implement a water conservation plan which maximizes efficiency of water use at the facility through conservation techniques and management practices; (4) Existing single pass cooling systems shall be eliminated and installation of new single pass cooling systems shall be prohibited. (b) Exemption. The requirements listed in subsection (a)(1) and (2) of this section are waived if the facility reuses one hundred (100) percent of its blowdown water. (Ord. No. 613, 5-20-96)