§ 13.11.040 — Installation of backflow prevention assemblies for fire system
Municipal Code of the City of Bullhead City, Arizona (Codified through Ordinance No. 2026-14, enacted August 17, 2026. (Supp. No. 75)) · Bullhead City Municipal Code § 13.11.040
Corpus is an independent public-information project, not the official City of Bullhead City website. Stable reference: corpuslaw.us/code/0cba3e8a-93bb-4cde-98ac-b2a9482104d8
13.11.040 - Installation of backflow prevention assemblies for fire system.
A. When a backflow prevention assembly is required for a water service connection supplying water only to a fire sprinkler system, the assembly shall be installed at the service connection in compliance with the standards and specification adopted by the utilities department. B. If the chief of the Bullhead City Fire Protection District or designee determines that a fire sprinkler system shall have a continuous water supply which may not be interrupted during testing of the backflow prevention assembly, the customer shall install at his own expense, two backflow prevention assemblies parallel to one another at the service connection. The diameter of each assembly shall be at least equal to the diameter of the service connection.
(Ord. No. 2021-15, § 1, 8-24-2021)