15.36.200 - Standards of construction.

In all special flood hazard areas the following standards are required: A. Anchoring. 1. All new construction and substantial improvements shall be anchored to prevent flotation, collapse or lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy; and 2. All manufactured homes shall meet the anchoring standards of Section 15.36.240.B. B. Construction Materials and Methods. 1. All new construction and substantial improvements shall be constructed with materials and utility equipment resistant to flood damage. 2. All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage. 3. All new construction, substantial improvement and other proposed new development shall be constructed with electrical, heating, ventilation, plumbing and air conditioning equipment and other service facilities that shall be designed and/or located to or above the regulatory flood elevation so as to prevent water from entering or accumulating within the components during conditions of flooding. 4. Require within Zones AH or AO that adequate drainage paths around structures on slopes guide floodwaters around and away from proposed or existing structures. C. Elevation and Floodproofing. 1. Residential construction, new or substantial improvement, shall have the lowest floor, including basement, elevated to or above the regulatory flood elevation: a. In an AO Zone, the base flood elevation is determined from the FIRM panel. If unspecified, the required elevation is at minimum two feet above highest adjacent grade. b. In an A Zone where the base flood elevation has not been determined, the base flood elevation is determined locally by the criteria set out in Section 15.36.190(C). c. In Zones AE and AH, the base flood elevation is determined from the FIS and/or FIRM. d. A garage attached to a residential structure, constructed with the garage floor slab below the regulatory flood elevation, must be designed to allow for the automatic entry and exit of flood waters and must be used solely for parking, access and/or storage. See Section 15.36.200(C)(3). e. Upon completion of the structure, the elevation of the lowest floor including basement shall be certified by a registered professional engineer or surveyor, and verified by the community's building inspector to be properly elevated. Such certification and verification shall be provided to the floodplain administrator. 2. Nonresidential construction, new, or substantial improvement, shall either be elevated in conformance with Section 15.36.200(C)(1) or together with attendant utility and sanitary facilities: a. Be floodproofed below the elevation recommended in Section 15.36.200(C)(1) so that the structure is watertight with walls substantially impermeable to the passage of water; and b. Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy; and c. Upon completion of the structure, certification by a registered professional engineer or surveyor that the elevation requirements of the lowest floor, including basement, of this section have been satisfied shall be provided to the floodplain administrator for verification; or certification by a registered professional engineer or architect that the floodproofing standards of this section are satisfied shall be provided to the floodplain administrator for verification. 3. Require, for all new construction and substantial improvements of nonresidential structures, with fully enclosed areas below the lowest floor that are useable solely for parking of vehicles, building access or storage in an area other than a basement and which are subject to flooding shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must meet or exceed the following minimum criteria: a. For non-engineered openings: 1. A minimum of two openings, on different sides of each enclosed area, having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding. 2. The bottom of all openings shall be no higher than one foot above grade. 3. Openings may be equipped with screens, louvers, valves or other coverings or devices provided that they permit the automatic entry and exit of floodwaters; or, b. For engineered openings: 1. Engineered openings (or covers and devices) that are specifically designed and certified by a registered engineer or architect as meeting the required performance and design requirements. 2. Engineered openings (or covers and devices) for which an Evaluation Report has been issued by the International Code Council (ICC) Evaluation Services, Inc. (ICC-ES), a subsidiary of the International Code Council, Inc. 4. Manufactured homes shall meet the standards in Section 15.36.240. 5. Accessory structures (detached garages and storage structures) used solely for parking of vehicles or storage may be constructed such that the floor is below the regulatory flood elevation, provided the structure is designed and constructed in accordance with the following requirements: a. Use of the accessory structure must be limited to parking of vehicles or storage; b. The portions of the accessory structure located below the regulatory flood elevation must be built using flood resistant materials. c. The accessory structure must be adequately anchored to prevent flotation, collapse and lateral movement. d. Any machinery or equipment servicing the accessory structure must be elevated or floodproofed to or above the regulatory flood elevation; e. The accessory structure must comply with floodway encroachment provisions in Section 15.36.245; and f. The accessory structure must be designated to allow for the automatic entry and exit of flood waters in accordance with the Section 15.36.200(C)(3) above. g. Detached garages, storage structures and other accessory structures not meeting the standards immediately above must otherwise be constructed in accordance with Section 15.36.200(C)(1) above. 6. Upon completion of the structure, evidence of compliance that demonstrates the requirements of this section have been satisfied shall be provided to the floodplain administrator for verification.

(Ord. No. 2024-28, § 1, 10-15-2024)

Ask a question about Bullhead City law

Corpus searches the Bullhead City sections it holds and shows the ones that match, with their citations. Free, no sign-in.