Sec. 10-93. - Types of protection.

(a) Required according to degree of hazard. The type of protection required shall depend on the degree of hazard which exists as follows: (1) An approved fixed air gap or an approved reduced pressure zone principle backflow prevention assembly shall be installed where the public water supply system may be contaminated causing a system health hazard. (2) An approved fixed proper air gap separation or an approved DC backflow prevention assembly shall be installed where the public water supply system may be polluted with substances that could cause a pollution hazard not dangerous to health. (b) More than one source. Any property with more than one water service shall, at the discretion of the department, have backflow protection on each service to the property. (c) Sand strainer. At the discretion of the department a strainer will be required on assemblies.

(Ord. No. 869, § I(7-14-6), 6-7-94)