§ 15.65.193 — Appendix C, Section C102.1, Minimum Number of Fire Hydrants for a Building—Amended
Municipal Code of the City of Bakersfield, California (Bakersfield Municipal Code current through Ordinance 5223, passed August 26, 2026 (municipal.codes publication, scraped 2026-11-17)) · Bakersfield Municipal Code § 15.65.193
Corpus is an independent public-information project, not the official City of Bakersfield website. Stable reference: corpuslaw.us/code/94aa9a4c-0197-49d5-bce8-06ecbb213342
15.65.193 Appendix C, Section C102.1, Minimum Number of Fire Hydrants for a Building—Amended.
Section C102.1, Minimum Number of Fire Hydrants for a Building, is amended to read as follows: C102.1 Minimum Number of Fire Hydrants for a Building. The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1. Table C102.1. REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS FIRE-FLOW REQUIREMENT (gpm) | MINIMUM NUMBER OF HYDRANTS | AVERAGE SPACING BETWEEN HYDRANTSa, b, c, f (feet) | MAXIMUM DISTANCE FROM ANY POINT ON STREET OR ROAD FRONTAGE TO A HYDRANTd, f FIRE-FLOW REQUIREMENT (gpm) | MINIMUM NUMBER OF HYDRANTS | AVERAGE SPACING BETWEEN HYDRANTSa, b, c, f (feet) | MAXIMUM DISTANCE FROM ANY POINT ON STREET OR ROAD FRONTAGE TO A HYDRANTd, f 1,750 or less | 1 | 500 | 250 1,751—2,250 | 2 | 450 | 225 2,251—2,750 | 3 | 450 | 225 2,751—3,250 | 3 | 400 | 225 3,251—4,000 | 4 | 350 | 210 4,001—5,000 | 5 | 300 | 180 5,001—5,500 | 6 | 300 | 180 5,501—6,000 | 6 | 250 | 150 6,001—7,000 | 7 | 250 | 150 7,001 or more | 8 or moree | 200 | 120