§ 13.16.050 — Backflow prevention assemblies—Type required

City Code, City of Buena Park, California (Includes legislation through Ord. No. 1769 adopted July 14, 2026) · Buena Park City Code § 13.16.050

Corpus is an independent public-information project, not the official City of Buena Park website. Stable reference: corpuslaw.us/code/f9cee4e6-8473-4831-9e52-91b93063cbbe

§ 13.16.050: Backflow prevention assemblies—Type required.

The type of protective assembly required for the premises shall depend upon the degree of hazard which exists, as follows: A. In the case of any premises where there is an auxiliary water supply as stated in subsection A of Section 13.16.040 of this chapter and it is not subject to any of the following rules, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention assembly. B. In the case of any premises where there is water or a substance that would be objectionable but not hazardous to health, if introduced into the public water system, the public water system shall be protected by an approved double-check valve backflow prevention assembly at each service connection. C. In the case of any premises where there is any material dangerous to health which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention assembly at each service connection. Examples of premises where these conditions exist include, but are not limited to, sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries and plating plants. D. In the case of any premises where there are uncontrolled cross-connections, either actual or potential, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention assembly at each service connection. E. In the case of any premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete in-plant cross-connection survey, the public water system shall be protected against back low from the premises by either an approved air-gap separation or an approved reduced pressure principle backflow prevention assembly on each service connection to the premises. F. In the event that the provisions of the CCCPH, as the same may be amended from time to time, or its successor provisions, pertaining to the type of backflow and cross-connection devices required to be installed for a given degree of hazard, mandate a different or more stringent requirement for a given degree of hazard, then such provisions of the CCCPH pertaining thereto shall apply notwithstanding the provisions of this section.

( Prior code § 33-104 ; Ord. 1223 § 2, 1988 ; amended during 1990 codification ; Ord. 1759 , 9/9/2025 )

Ask a question about Buena Park law

Corpus searches the Buena Park sections it holds and shows the ones that match, with their citations. Free, no sign-in.