§ 15.25.130 — Addition - Section 404.5.1 - Increased Fire Flow for Subdivisions in Very High Fire Hazard Severity Zones

Corona, California, Municipal Code (2026 S-57: Local legislation passed through Ord. 3427, passed 4-1-2026) · Corona Municipal Code § 15.25.130

Corpus is an independent public-information project, not the official City of Corona website. Stable reference: corpuslaw.us/code/c49a871a-8328-48bf-b658-6367fb5ffffb

15.25.130 Addition - Section 404.5.1 - Increased Fire Flow for Subdivisions in Very High Fire Hazard Severity Zones.

Section 404.5.1 is added to read as follows: "404.5.1 Increased Fire Flow for Subdivisions in Very High Fire Hazard Severity Zones. (a) General. For new residential subdivisions consisting of five (5) or more lots for one and two family dwellings located within a Very High Fire Hazard Severity Zone (VHFHSZ), as designated by the Director of Forestry and Fire Protection, the minimum fire-flow requirements shall be increased in accordance with this section. (b) Fire-Flow Requirements. (1) The required fire flow shall be not less than 2,000 gallons per minute (GPM) at a residual pressure of 20 psi for a minimum duration of 2 hours. (2) Where any dwelling unit exceeds 3,600 square feet of floor area, the required fire flow shall be increased to 2,500 gpm for a minimum duration of 2 hours. (c) Wildland Technical Standard. Where the entire subdivision is constructed in compliance with the most current version of IBHS Wildfire Prepared Neighborhood Technical Standard, the required fire flow shall comply with the standard fire-flow requirements set forth in Table B105.1 of the California Fire Code, as amended by Section 15.12.370 of the Corona Municipal Code. (d) Fire Hydrant Spacing and Distribution. (1) Fire hydrants shall be installed pursuant Table C102.1 of the California Fire Code, as amended by Section 15.12.380 of the Corona Municipal Code. (2) Each hydrant shall be capable of delivering the fire flow required by this section. (e) Alternative Methods. Where the existing water system cannot support the minimum required fire flow, the fire code official is authorized to approve alternative methods of protection, including but not limited to: (1) On-site water storage tanks with fire department connections, (2) Residential fire sprinklers in accordance with NFPA 13R or NFPA 13. (f) Exception. The following shall comply with the standard fire-flow requirements set forth in Table B105.1 of the California Fire Code, as amended by Section 15.12.370 of the Corona Municipal Code without modification: (1) Residential subdivisions of fewer than five (5) lots. (2) Residential subdivisions for multi-family dwellings. (3) Residential subdivisions located outside of the VHFHSZ. (Ord. 3421 § 12 (part), 2025.)

Ask a question about Corona law

Corpus searches the Corona sections it holds and shows the ones that match, with their citations. Free, no sign-in.