§ 12.20.250 — GREASE INTERCEPTOR MAINTENANCE REQUIREMENTS
Fullerton, California, Code of Ordinances (2026 S-1: Local legislation current through Ord. 3352) · Fullerton Municipal Code § 12.20.250
Corpus is an independent public-information project, not the official City of Fullerton website. Stable reference: corpuslaw.us/code/1fc601ad-c7a3-4896-8839-76ed7d7dffe8
§ 12.20.250 GREASE INTERCEPTOR MAINTENANCE REQUIREMENTS.
(A) Grease interceptors shall be maintained in efficient operating condition by periodic removal of the full content of the interceptor which includes wastewater, accumulated FOG, floating materials, sludge and solids. (B) All existing and newly installed grease interceptors shall be maintained in a manner consistent with a maintenance frequency approved by the FOG Control Program Manager pursuant to this section. (C) No FOG that has accumulated in a grease interceptor shall be allowed to pass into any sewer lateral, sewer system, storm drain or public right-of-way during maintenance activities. (D) Food service establishments with grease interceptors may be required to submit data and information necessary to establish the maintenance frequency grease interceptors. (E) The maintenance frequency for all food service establishments with a grease interceptor shall be determined in one of the following methods. (1) Grease interceptors shall be fully pumped out and cleaned at a frequency such that the combined FOG and solids accumulation does not exceed 25% of the total liquid depth of the grease interceptor. This is to ensure that the minimum hydraulic retention time and required available volume is maintained to effectively intercept and retain FOG discharged to the sewer system. (2) All food service establishments with a grease interceptor shall maintain their grease interceptor not less than once every six months. (3) Grease interceptors shall be fully pumped out and cleaned quarterly when the frequency described in division (E)(1) above has not been established. The maintenance frequency shall be adjusted when sufficient data have been obtained to establish an average frequency based on the requirements described in division (E)(1) above and guidelines adopted pursuant to the FOG Control Program. The city may change the maintenance frequency at any time to reflect changes in actual operating conditions in accordance with the FOG Control Program. Based on the actual generation of FOG from the food service establishment, the maintenance frequency may increase or decrease. (4) The owner/operator of a food service establishment may submit a request to the FOG Control Program Manager requesting a change in the maintenance frequency at any time. The food service establishment has the burden of responsibility to demonstrate that the requested change in frequency reflects actual operating conditions based on the average FOG accumulation over time and meets the requirements described in division (E)(1) above, and that it is in full compliance with the conditions of its permit and this chapter. Upon determination by the FOG Control Program Manager that requested revision is justified, the permit shall be revised accordingly to reflect the change in maintenance frequency. (5) If the grease interceptor, at any time, contains FOG and solids accumulation that exceeds the maximum allowable limits described in division (E)(1) above, the food service establishment shall be required to have the grease interceptor serviced immediately such that all fats, oils, grease, sludge and other materials are completely removed from the grease interceptor. If deemed necessary, the FOG Control Program Manager may also increase the maintenance frequency of the grease interceptor from the current frequency. (Ord. 3051, passed - -2004)
Ask a question about Fullerton law
Corpus searches the Fullerton sections it holds and shows the ones that match, with their citations. Free, no sign-in.