§ 13.20.230 — KEY BOXES, AMENDED
Fullerton, California, Code of Ordinances (2026 S-1: Local legislation current through Ord. 3352) · Fullerton Municipal Code § 13.20.230
Corpus is an independent public-information project, not the official City of Fullerton website. Stable reference: corpuslaw.us/code/ed6ec396-72c3-445c-b2fd-31c3f8bdc78a
§ 13.20.230 KEY BOXES, AMENDED.
SECTION 506 KEY BOXES Section 506.1 Where Required. (Amended) Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for emergency or non-emergency response purposes, the fire code official is authorized to require a key box, lock or key switch to be installed in an accessible location. The key box, switch, or lock shall be of an approved type listed in accordance with UL 1037, and all key boxes shall contain keys to gain necessary access a required by the fire code official. Section 506.3 Gate Emergency Access (Added) Required gates or barricades. The fire code official is authorized to require the installation and maintenance of gates or other approved barricades across fire apparatus access roads, trails, or other accessways, not including public streets, alleys, or highways. Installations shall meet the following: 1. Electric gate operators, where provided shall be listed in accordance with UL 325. 2. Gates intended for automatic operation shall be designed, constructed, and installed to comply with the requirements of ASTM F 2200 and must be equipped with "Click 2 Enter" or similar equipment that is approved by the fire code official, that allows for operations of the gate by fire and police personnel via their vehicle mobile radio, on a dedicated radio frequency, with a hold-open for a specified amount of time. 3. Gates over the fire apparatus access road that are intended for automatic operation shall be designed to operate during a loss of power or fail in the open position. 4. Gates shall be at a minimum as wide as the required access road width. 5. If manually operated, a Knox padlock is required if the gate is locked. 6. Installations must be set back 40 feet from the roadway edge of pavement. Exception: Automated gates meeting the requirements of item 2 of this subsection. (Ord. 3317, passed - -2022; Ord. 3349, passed - -2025)
Ask a question about Fullerton law
Corpus searches the Fullerton sections it holds and shows the ones that match, with their citations. Free, no sign-in.