§ 14.04.120 AMENDMENT TO § R902.1.
Section R902.1 of Chapter 9 of the 2025 Edition of the California Residential Code, is hereby amended to read as follows: R902.1 Roof assemblies. Roofs shall be covered with materials as set forth in Sections R904 and R905. A minimum Class A or B roofing shall be installed in areas designated by this section or where the edge of the roof is less than 3 feet (914 mm) from a lot line. Class A or B roofing required by this section to be listed shall be tested in accordance with UL 790 or ASTM E108. Where required, the roof assembly shall be listed and identified as to class by an approved testing agency. Exceptions: 1. Class A roof assemblies include those with coverings of brick, masonry and exposed concrete roof deck. 2. Class A roof assemblies include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible decks. 3. Class A roof assemblies include minimum 16 ounces per square foot copper sheets installed over combustible decks. 4. Class A roof assemblies include slate installed over underlayment over combustible decks. (Ord. 3316, passed - -2022; Ord. 3348, passed - -2025)