SEC. 5-3.500 - FIRE HYDRANTS. HOSE.
In every mobile home park or portion thereof that contains ten (10) or more mobile home sites, there shall be installed and maintained approved fire hydrants with mounted hose rack or reel in weather-protected cabinets spaced at such distances as to reach all areas with seventy-five (75) feet of hose. Each fire hydrant shall not be less than one and one-half (1½) inches in diameter and terminated with an approved gated shut-off valve. Water system piping shall have an internal diameter sufficient to deliver fifty (50) gallons of water per minute at thirty (30) pounds per square inch of pressure at any hose connection. In no case shall such water piping system be less than two (2) inches internal diameter. Hose racks or reels shall be equipped with seventy-five (75) feet of one and one-half (1½) inch diameter Underwriters approved or equal fire hose with attached nozzles having one-half (½) inch tips.