§ 6-5-405 — Location of tanks

Irvine Municipal Code (Supp. No. 20: codified through Ordinance No. 26-05, adopted February 10, 2026) · Irvine Municipal Code § 6-5-405

Corpus is an independent public-information project, not the official City of Irvine website. Stable reference: corpuslaw.us/code/00457a64-f23a-4b23-8c2a-8e256e000926

Sec. 6-5-405. - Location of tanks.

Minimum distance between any outside aboveground tank to the nearest building or line of adjoining property which may be built upon: A. Flammable liquids other than those having boil-over characteristics similar to crude petroleum: Class of Flammable Liquid | Capacity of Tank | Minimum Distance III | 0 to 275 gals. | 0 feet III | 276 to 750 gals. | 5 feet I and II | 0 to 750 gals. | 10 feet III | 751 to 12,000 gals. | 10 feet I and II | 751 to 12,000 gals. | 15 feet I, II and III | 12,001 to 24,000 gals. | 15 feet I, II and III | 24,001 to 30,000 gals. | 20 feet I, II and III | 30,001 to 50,000 gals. | 25 feet B. Crude petroleum and other liquids having boil-over characteristics similar to crude petroleum and flammable liquid tanks with capacity in excess of 50,000 gallons: _____ STORAGE FACILITIES Crude Petroleum and Tanks with Capacities in Excess of 50,000 Gallons Tanks with capacities in excess of 50,000 gallons and all tanks for the storage of crude petroleum shall be located in accordance with the following provisions (applicable to gastight tanks including conservation type tanks constructed in compliance with these or equivalent standards): Product Stored | Group | Tank Protection | Distance From Line Adjoining Property Which May Be Built Upon Shall Be Not Less Than: Refined Petroleum Products or other flammable liquids not subject to boil-over. | Group A Tanks | 1) An approved permanently attached extinguishing system or 2) An approved floating roof. | Greatest dimension of diameter or height of tank, except that such distance need not exceed 120 feet. Group B Tanks | Not equipped with either of the above. | 1½ times the greatest dimension of diameter or height of tank except that such distance need not exceed 175 feet. Group C Tanks | 1) An approved permanently attached extinguishing system or 2) An approved floating roof. | 2 times the greatest dimension of diameter or height of tank except that such distance shall not be less than 20 feet and need not exceed 175 feet. Crude petroleum | Group D Tanks | Not equipped with either of the above. | 3 times the greatest dimension of diameter or height of tank except that such distance shall not be less than 20 feet and need not exceed 350 feet. _____ 1. Group A Tanks. Any gastight tank constructed in compliance with these or equivalent standards and equipped either with: a. An approved permanently attached extinguishing system; or b. An approved floating roof, which is to be used only for the storage of refined petroleum products or other flammable liquids not subject to boil-over, shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than the greatest dimension of diameter or height of the tank, except that such distance need not exceed 120 feet. 2. Group B Tanks. Any gastight tank constructed in compliance with these or equivalent standards but not equipped either with: a. An approved permanently attached extinguishing system; or b. An approved floating roof, which is to be used only for the storage of refined petroleum products or other flammable liquids not subject to boil-over, shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than 1½ times the greatest dimension of diameter or height of the tank, except that such distance need not exceed 175 feet. 3. Group C Tanks. Any gastight tank constructed in compliance with these or equivalent standards and equipped either with: a. An approved permanently attached extinguishing system; or b. An approved floating roof, which is to be used for the storage of crude petroleum, shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than twice the greatest dimension of diameter or height of the tank, except that such distance shall be not less than 20 feet and need not exceed 175 feet. 4. Group D Tanks. Any gastight tank constructed in compliance with these or equivalent standards and not equipped either with: a. An approved permanently attached extinguishing system; or b. An approved floating roof, which is to be used for the storage of crude petroleum, shall be so located that the distance from the line of adjoining property which may be built upon shall be not less than three times the greatest dimension of diameter or height of the tank, except that such distance shall not be less than 20 feet and need not exceed 350 feet. NOTE: The term "approved attached extinguishing system," as used in the foregoing description, may be interpreted to apply to: (1) A fixed foam or other recognized extinguishing system embodying a supply of the extinguishing medium; or (2) A system employing a pipeline for conveying foam from a point outside the dike to the tank; or (3) Portable overshot devices for applying foam over the rim of the tank. Where reliance is placed on a pipeline for conveying foam, the pipeline shall be so installed and attached as to be an integral part of the tank. Where reliance is placed on a portable overshot device, the practicability of its use shall be demonstrated before approval. Approved foam generating equipment of sufficient capacity should be available on the property, by response of a municipal or other public Fire Department, or otherwise readily available; and there should be on hand or otherwise readily available a sufficient supply of foam-producing materials as specified in NFPA Standards for Foam Extinguishing Systems, No. 11; or (4) Buildings essential to the operation of the storage facilities: Building location. No building used for human occupancy, except buildings essential to the operation of the storage facilities, shall be erected within the distances set out in the tables above, from such storage tanks. The term gastight tank includes, for the purposes of this section, so-called conservation type tanks.

(Code 1976, § VI.I-405; Ord. No. 27, § 77.0112(e), 4-17-72)

Ask a question about Irvine law

Corpus searches the Irvine sections it holds and shows the ones that match, with their citations. Free, no sign-in.